| 2013-02-28 10:29:16 | 1. PLEASE PROVIDE INFORMATION TO CONFIRM THE NEW GRADE |
| | FOR THE ENTRANCE ALONG EVERNIA STREET IS NOT AFFECTING |
| | THE ROW ELEVATION ALONG THE SIDEWALK, ACCORDING TO THE |
| | SURVEY THE BACK OF SIDEWALK ELEVATION IS 40.83' AND THE |
| | BUILDING FINISHED FLOOR IS AT 43'. THE SIDEWALK |
| | CROSSLOPE CANNOT EXCEED 2%. |
| | 2. BIKE RACKS IN FRONT OF LOBBY ARE OK. PROPOSED BIKE |
| | RACKS INSIDE PARKING GARAGE IS NOT INSTALLED TO |
| | PROPERLY ALLOW 6 BIKE SPACES. PLEASE FOLLOW GUIDELINES |
| | WITH DIMENSIONS (30" BEWTEEN RACKS, 24" SEPARATION FROM |
| | WALLS OR OTHER OBSTRUCTIONS. PLEASE SEE GUIDELINES |
| | PROVIDED). |
| | 3. PLEASE CORRECT THE HATCH ON ALL FLOOR PLANS TO |
| | ACCURATELY REFLECT THE FAR CALCULATIONS (HATCH ONLY |
| | AREAS NOT INCLUDED IN THE FAR). STAIRS AND ELEVATOR |
| | WITHIN THE PARKING LEVEL SHALL BE INCLUDED IN THE FAR, |
| | PLEASE ADJUST TABLE TO REFLECT. |
| | 4. ALL MECHANICAL EQUIPMENT SHALL BE ENCLOSED AND |
| | SCREENED AS AN INTEGRAL PART OF THE BUILDING DESIGN AS |
| | REQUIRED BY THE DAC SPECIAL REVIEW APPROVAL. THE |
| | PROPOSED PARAPET WALL SHALL SCREEN THE EQUIPMENT FROM |
| | THE VIEW OF A PERSON AT GROUND LEVEL. ADDITIONAL |
| | SCREENING SHALL BE PROVIDED FOR AERIAL VIEW. AS THE |
| | EQUIPMENT IS LOW A ROOF-LIKE SCREEN WILL MEET THE |
| | INTENT OF THE CODE. |
| | 5. THE TREE CANOPY REQUIRED FOR THE PRIVATE OPEN SPACE |
| | SHALL BE PROVIDED WITHIN THE PRIVATE OPEN SPACE. THE |
| | REQUIRED PRIVATE OPEN SPACE CALCULATION SHALL NOT |
| | INCLUDE THE GRASSED AREA ADJACENT TO THE ALLEY. |
| | 6. PROPOSED LANDSCAPE AREA WITHIN THE 5TH FLOOR ROOF |
| | TOP TERRACE CAN BE ENHANCED TO AT LEAST MEET 50% OF THE |
| | VEGETATED AREA REQUIRED FOR A PRIVATE OPEN SPACE. |
| | ADDITIONAL PLANER BOXES ARE SUGGESTED. |
| | 7. PLEASE UPDATE THE FACADES TO REFLECT THE CHANGES IN |
| | THE BUILDING ENTRANCE. |
| | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA |
| | APONTE AT 561-822-1439. |
| |