Plan Review Notes
Plan Review Notes For Project Z12110018
Project Number Z12110018
Review Stop STORM
Sequence Number 1
Notes
Date Text
2012-12-10 16:33:491. SFWMD ERP REQUIRED BEFORE START OF
 CONSTRUCTION/DEMOLITION.
 2. EROSION CONTROL PLAN AND STORM WATER POLLUTION
 PREVENTION PLAN REQUIRED WITH ENGINEERING PERMIT
 APPLICATION.
 3. NO DRAINAGE CALCULATIONS PROVIDED. CALCULATIONS WILL
 BE NEEDED WITH THE ENGINEERING PERMIT APPLICATION.
 4. NO ENGINEERING PLANS PROVIDED OTHER THAN ENGINEERING
 SITE PLAN.
 5. AVOID LOCATING TREES ADJACENT TO UNDERGROUND UTILITY
 LINES.
 6. OAK TREES NEAR YARD DRAINS WILL RESULT IN
 LEAVES/ACORNS ACCUMULATING IN/ON YARD DRAIN.
 7. EXISTING CURB INLET ON TAMARIND AVE, POINT OF
 PROPOSED DRAINAGE CONNECTION, MAY HAVE TO BE REPLACED
 DEPENDING ON CURRENT CONDITION OF THE INLET.
 8. CONSIDER MOVING FIRE LINES TO BUILDINGS A1 AND A2
 FURTHER NORTH AND CLOSER TO INLET TO AVOID THE BREAK IN
 THE EXFILTRATION TRENCH SOUTH OF THE INLET.
 9. NOTE ON ENGINEERING SITE PLAN INDICATES EXISTING ROW
 TO BE ABANDONED. SURVEY INDICATES DOUGLAS AVE ROW QUIT
 CLAIMED TO PALM BEACH HOUSING AUTHORITY.
 10. NO SIDEWALK PROPOSED ALONG THE SOUTH SIDE OF GRANT
 STREET ALONG THE NORTH PROPERTY LINE?
 11. HOW WILL DRAINAGE IN 50' EASEMENT ACCOMMODATE
 FUTURE ROAD IN THIS EASEMENT?
 12. LEGAL DESCRIPTION OF PROPERTY - PLAT OF DUNBAR
 VILLAGE RECORDED ON PAGE 77 (NOT 177) OF PLAT BOOK 18.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120