2012-12-10 15:18:571. NO DRAINAGE CALCULATIONS PROVIDED.
 2. MINIMUM WAER QUALITY TREATMENT TO BE PROVIDED ONSITE
 FOR EACH DEVELOPMENT NORTH AND SOUTH OF THE ALLEY TO
 EQUAL TO THE GREATER OF 1" OF RUNOFF OR 2.5" TIMES
 PERCENT IMPERVIOUSNESS.
 3. SFWMD ERP OR EXEMPTION LETTER REQUIRED BEFORE START
 OF CONSTRUCTION/DEMOLITION.
 4. EROSION CONTROL PLAN AND STORM WATER POLLUTION
 PREVENTION PLAN REQUIRED WITH ENGINEERING PERMIT
 APPLICATION.
 5. SHOW PROPOSED UTILITIES ON LANDSCAPE PLAN.
 6. PROPOSED CONTROL STRUCTURE WITH WEIR TO BE LOCATION
 ONSITE AND NOT IN THE RIGHT-OF-WAY.
 7. POTENTIAL CONFLICT BETWEEN TREES AND PROPOSED STORM
 PIPE WEST OF THE PROPOSED CONTROL STRUCTURE ON HIBISCUS
 STREET.
 8. AT EAST DRIVEWAY ENTRANCE ON HIBISCUS STREET,
 MISSING STORM PIPE OR ERRANT LABEL (PROP. DRAINAGE
 PIPE)?
 9. EX. 18" RCP LOCATED EAST OF HIBISCUS STREET EAST
 DRIVEWAY SHOULD BE PLUGGED AT MANHOLE AND THE PIPE
 NORTH OF THE MANHOLE FILLED WITH FLOWABLE FILL OR
 REMOVED.
 10. SHOW EXISTING INLET IN DRIVEWAY AT NORTHWEST CORNER
 OF DIXIE HWY AND HIBISCUS STREET.
 11. ROOF DRAINS TO BE HARD PIPED INTO THE ONSITE
 DRAINAGE SYSTEM.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120