| 2012-07-30 23:56:18 | 7/30/12 PLANS REVIEWED BY FIRE **DENIED** |
| | |
| | 1. SHOW SCOPE OF WORK ON PLANS. |
| | |
| | 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE |
| | FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA |
| | EDITION OF NFPA 1 AND NFPA 101. |
| | |
| | 3. ALL DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. |
| | |
| | 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | 5. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY |
| | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| | TRAVEL ETC. |
| | |
| | 6. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | 7. PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | 8. PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2 |
| | OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1). |
| | |
| | 9. STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | 10. PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS |
| | WITH EXIT SIGNS. |
| | |
| | 11. STAIRS AND EGRESS COMPONENTS SHALL CONFORM TO THE |
| | LIFE SAFETY REQUIREMENTS OF CHAPTER 7 OF NFPA 101 |
| | FLORIDA 2010 EDITION. |
| | |
| | |
| | DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | OFFICE OF THE FIRE MARSHAL |
| | (561) 805-6733 |
| | |
| |