Plan Review Notes
Plan Review Notes For Project Z12060017
Project Number Z12060017
Review Stop STORM
Sequence Number 1
Notes
Date Text
2012-07-10 11:30:221. COORDINATE DRAINAGE DESIGN WITH PROPOSED FIRE
 STATION NO. 5 EOC DRAINAGE SYSTEM.
 2. CONSTRUCTION EASEMENT MAY BE NEEDED TO WORK ON FIRE
 STATION NO. 5 SITE.
 3. MAINTAIN PROPER CLEARANCE BETWEEN SANITARY SEWER AND
 DRAINAGE STRUCTURE WEST OF BUILDING 13.
 4. PROVIDE BREAK IN EXFILTRATION TRENCH WHERE OTHER
 UTILITIES CROSS THE STORM PIPES.
 5. INDICATE WHERE THE CONTROL WEIRS WILL BE BETWEEN THE
 EXFILTRATION TRENCHES AND "LAKES".
 6. SHEETS 5 AND 6 INCORRECTLY TITLED (W&S DETAILS VS.
 P&D DETAILS).