Plan Review Notes
Plan Review Notes For Project Z12040011
Project Number Z12040011
Review Stop STORM
Sequence Number 1
Notes
Date Text
2012-05-09 07:26:431. WHY 15' EXFILTRATION TRENCH DEPTH?
 2. STORMWATER RUNOFF FROM WESTERN 1/3 OF PARKING LOT
 NOT GETTING WATER QUALITY TREATMENT.
 3. PROVIDE COPY OF SFWMD ERP PERMIT FOR PROPOSED WORK.
 4. PROVIDE DRAINAGE CALCULATIONS SIGNED AND SEALED BY A
 FLORIDA P.E. SHOWING LAND USE BREAKDOWN (PERVIOUS,
 IMPERVIOUS, BUILDING, ETC.), WATER QUALITY TREATMENT
 VOLUMES (REQUIRED, PROVIDED) AND DESIGN STORM FLOOD
 STAGES (5-YEAR 24-HOUR, 25-YEAR 72-HOUR AND 100-YEAR
 72-HOUR ZERO DISCHARGE).
 5. FINAL PLANS TO INCLUDE STORM WATER POLLUTION
 PREVENTION PLAN.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT