Plan Review Notes
Plan Review Notes For Project Z12040009
Project Number Z12040009
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-07-06 19:01:37PLANS REVIEWED BY FIRE ***DENIED***
  
  
 1.) DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 2.) ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 3.) FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE
 DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT
 LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES
 PER SECTION 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION
 CODE ? NFPA 1 UNIFORM FIRE CODE.
 4.) PROVIDE DETAILED INFROMATION ON LOCATION OF FDC.
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6733
  