Plan Review Notes
Plan Review Notes For Project Z12040009
Project Number Z12040009
Review Stop STORM
Sequence Number 1
Notes
Date Text
2012-05-09 08:09:171. NO CIVIL ENGINEERING PLANS PROVIDED.
 2. PROVIDE COPY OF SFWMD ERP CONSTRUCTION PERMIT WITH
 FINAL PLANS.
 3. PROVIDE STORM WATER POLLUTION PREVENTION PLAN WITH
 FINAL PLANS.
 4. PROVIDE DRAINAGE CALCULATIONS SIGNED AND SEALED BY A
 FLORIDA P.E. SHOWING LAND USE BEAKDOWN (PERVIOUS,
 IMPERVIOUS, BUILDING, ETC.), WATER QUALITY TREATMENT
 VOLUMES (REQUIRED, PROVIDED) AND DESIGN STORM FLOOD
 STAGES (5-YEAR 24-HOUR, 25-YEAR 72-HOUR AND 100-YEAR
 72-HOUR ZERO DISCHARGE).
 5. PROVIDE AN INSPECTION REPORT OF THE STORM PIPE
 CULVERTS WITHIN THE 50' DRAINAGE EASEMENT ALONG THE
 NORTH SIDE OF THE SITE.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 OFFICE 561-494-1120