| Plan Review Notes For Project Z12040009 |
| Project Number |
Z12040009 |
|
| Review Stop |
STORM |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-09 08:09:17 | 1. NO CIVIL ENGINEERING PLANS PROVIDED. | | | 2. PROVIDE COPY OF SFWMD ERP CONSTRUCTION PERMIT WITH | | | FINAL PLANS. | | | 3. PROVIDE STORM WATER POLLUTION PREVENTION PLAN WITH | | | FINAL PLANS. | | | 4. PROVIDE DRAINAGE CALCULATIONS SIGNED AND SEALED BY A | | | FLORIDA P.E. SHOWING LAND USE BEAKDOWN (PERVIOUS, | | | IMPERVIOUS, BUILDING, ETC.), WATER QUALITY TREATMENT | | | VOLUMES (REQUIRED, PROVIDED) AND DESIGN STORM FLOOD | | | STAGES (5-YEAR 24-HOUR, 25-YEAR 72-HOUR AND 100-YEAR | | | 72-HOUR ZERO DISCHARGE). | | | 5. PROVIDE AN INSPECTION REPORT OF THE STORM PIPE | | | CULVERTS WITHIN THE 50' DRAINAGE EASEMENT ALONG THE | | | NORTH SIDE OF THE SITE. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | OFFICE 561-494-1120 |
| |