Plan Review Notes
Plan Review Notes For Project Z11120014
Project Number Z11120014
Review Stop STORM
Sequence Number 1
Notes
Date Text
2012-01-30 06:57:291. MATCH SECTION OF EXISTING 'F' CURB AND GUTTER
 2. WHERE WILL ROOF DRAINS DISCHARGE?
 3. ACCOMMODATE ROOF DOWN SPOUT OF ADJACENT BUILDING.
 4. NO DRAINAGE CALCULATIONS PROVIDED.
 5. STORMWATER TREATMENT VOLUMES TO BE PROVIDED PER
 SFWMD CRITERIA.
 6. EROSION AND SEDIMENT CONTROL PLAN WILL BE REQUIRED.
  