2012-03-01 11:38:3102/07/2012 PLANNING BOARD CASE NO. 11-02 (Z11120014)
 335 CLEMATIS STREET
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 1. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 2. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 3. THE ENTRANCE INTO THE VALET SERVICES SHOWS THE FLOW
 OF TRAFFIC TRAVELING IN THE WRONG DIRECTION (NORTH) ON
 DIXIE HIGHWAY. ONE WAY TRAFFIC (SOUTH) EXITS AT THIS
 LOCATION.
 4. LOCATE THE FIRE PUMP ROOM ON THE FIRST FLOOR;
 PREFERABLY WITH EXTERIOR ACCESS.
 5. SEVERAL OF THE DOORS ON THE THIRD FLOOR AND ROOF
 (ASSEMBLY OCCUPANCY) SWING AGAINST THE PATH OF EGRESS.
 6. INDICATE THE LOCATION FOR EMERGENCY VEHICLES TO
 PARK/STAGE DURING A MEDICAL OR FIRE EMERGENCY.
  
  
  
  
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW