| 2012-02-08 10:15:39 | BUILDING REVIEW COMMENTS | | | | | | | | | | | | BUILDING PERMIT APPLICATIONS SUBMITTED AFTER MARCH 15TH | | | 2012 WILL BE REVIEWED WITH THE FLORIDA BUILDING CODE ( | | | FBC ) 2010 EDITION. | | | | | | ALL PUBLIC USE AREAS SHALL BE ACCESSIBLE PER FBC | | | CHAPTER 11. IDENTIFY REQUIRED ACCESSIBLE SLEEPING | | | ROOMS. | | | | | | PLEASE SEE FBC SECT. 505 FOR MEZZANINE REQUIREMENTS IE: | | | ALLOWABLE AREA, EGRESS AND VERTICAL ACCESSIBILITY. | | | | | | SEE FBC 1024 EXCEPTION: 1.1, YOUR INTERIOR STAIR EXIT | | | DISCHARGE SHALL OPEN TO A FREE AND UNOBSTRUCTED WAY TO | | | THE EXTERIOR OF THE BUILDING READILY VISIBLE AND | | | IDENTIFIABLE. EXIT CAPACITY CALCULATIONS SHOWING LESS | | | THAN 50% OF TOTAL OCCUPANCY WILL BE REQUIRED ON THE | | | LIFE SAFETY PLAN. | | | | | | PROVIDE ALLOWABLE OPENING AREA CALCULATIONS FOR THE | | | NORTH AND EAST ELEVATIONS, SEE FBC 704.8. ALSO SHOW | | | COMPLIANCE WITH 704.9 FOR VERTICAL SEPARATION OF | | | OPENINGS. | | | | | | FBC 1406.2 WILL APPLY FOR ANY COMBUSTIBLE MATERIALS. | | | | | | PAGE A-1, CLEMATIS ST. EXIT STAIR DOOR SEEMS TO BE | | | SLIGHTLY ENCROACHING THE PUBLIC RIGHT OF WAY WHEN FULLY | | | OPEN. | | | | | | | | | | | | | | | THANK YOU, | | | LUIS MARTINEZ | | | 561-805-6710 | | | | | | | | | |
| |