2012-02-08 10:15:39BUILDING REVIEW COMMENTS
  
  
  
 BUILDING PERMIT APPLICATIONS SUBMITTED AFTER MARCH 15TH
 2012 WILL BE REVIEWED WITH THE FLORIDA BUILDING CODE (
 FBC ) 2010 EDITION.
  
 ALL PUBLIC USE AREAS SHALL BE ACCESSIBLE PER FBC
 CHAPTER 11. IDENTIFY REQUIRED ACCESSIBLE SLEEPING
 ROOMS.
  
 PLEASE SEE FBC SECT. 505 FOR MEZZANINE REQUIREMENTS IE:
 ALLOWABLE AREA, EGRESS AND VERTICAL ACCESSIBILITY.
  
 SEE FBC 1024 EXCEPTION: 1.1, YOUR INTERIOR STAIR EXIT
 DISCHARGE SHALL OPEN TO A FREE AND UNOBSTRUCTED WAY TO
 THE EXTERIOR OF THE BUILDING READILY VISIBLE AND
 IDENTIFIABLE. EXIT CAPACITY CALCULATIONS SHOWING LESS
 THAN 50% OF TOTAL OCCUPANCY WILL BE REQUIRED ON THE
 LIFE SAFETY PLAN.
  
 PROVIDE ALLOWABLE OPENING AREA CALCULATIONS FOR THE
 NORTH AND EAST ELEVATIONS, SEE FBC 704.8. ALSO SHOW
 COMPLIANCE WITH 704.9 FOR VERTICAL SEPARATION OF
 OPENINGS.
  
 FBC 1406.2 WILL APPLY FOR ANY COMBUSTIBLE MATERIALS.
  
 PAGE A-1, CLEMATIS ST. EXIT STAIR DOOR SEEMS TO BE
 SLIGHTLY ENCROACHING THE PUBLIC RIGHT OF WAY WHEN FULLY
 OPEN.
  
  
  
  