Plan Review Notes
Plan Review Notes For Project Z11120013
Project Number Z11120013
Review Stop STORM
Sequence Number 1
Notes
Date Text
2012-01-31 08:34:561. TYPICAL PARALLEL PARKING DETAILS ON SHEET #RP-1
 INCOMPLETE.
 2. FINAL ENGINEERING PLANS SHOULD CONTAIN SECTIONS FOR
 PROPOSED PARKING LOTS.
 3. FINAL ENGINEERING PLANS SHOULD CONTAIN PAVING AND
 DRAINAGE DETAILS.
 4. ADVISORY NOTE: DRAINAGE CALCULATIONS SHALL
 DEMONSTRATE PROPOSED DRAINAGE SYSTEM ADHERES TO SFWMD
 ENVIRONMENTAL RESOURCES PERMITTING CRITERIA.
  
 TRACY L. WARD, P.E.
 SENOIR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 TELEPHONE 561-494-1120
  
2012-01-06 08:12:431. NO CIVIL ENGINEERING PLANS PROVIDED.
 2. STORMWATER SYSTEM TO BE DESIGNED TO MEET SFWMD
 CRITERIA.
 3. TREES SHOULD HAVE A MINIMUM 5-FOOT SEPARATION
 BETWEEN TRUNK AND OUTSIDE OF EXFILTRATION TRENCHES.
 4. SURVEY AND SITE PLAN/LANDSCAPE PLAN AT DIFFERENT
 SCALES.
  
 TRACY WARD
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 TELEPHONE 561-494-1120