2011-12-29 09:39:35PLANS AND PLATS REVIEW COMMITTEE (PPRC)
 JANUARY 11, 2012 MEETING
 PLANNING BOARD CASE NO. 1594A (Z1120013)
 HULETT OFFICE BUILDING
 7640 OKEECHOBEE BOULEVARD
  
 1. ON SHEET SP-1 KNOX-BOXES ARE CALLED OUT ON THE
 DRAWING. THESE BOXES CAN BE ORDERED AT WWW.KNOXBOX.COM.
 THE KNOX BOXES ARE TO BE WEST PALM BEACH FIRE RESCUE
 APPROPRIATE.
  
 2. SECURITY GATES REQUIRE SEPARATE PLANS AND PERMITS
 PRIOR TO INSTALLATION.
  
 3. THE BUILDING ADDRESS DISPLAYED ON THE PLANS SHALL BE
 A MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE THAT
 CONTRAST TO THE BACKGROUND THEY ARE AFFIXED TO.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 GENERATOR AND FUEL TANKS.
  
 5. THE PROPOSED THREE-STORY BUILDING WILL BE REQUIRED
 TO BE FIRE SPRINKLER PROTECTED. SEPARATE PLANS AND
 PERMITS REQUIRED PRIOR TO INSTALLATION.
  
 6. SUBMIT COMPLETE PLANS TO THE CONSTRUCTION SERVICES
 DEPARTMENT FOR REVIEW.
  
 7. A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.
  
 8. PROPER TENANT SEPARATIONS WILL BE REQUIRED IF
 MULTIPLE TENANTS ARE EXPECTED.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM.
  
 10. EXITS ARE TO BE KEPT UP WITH CONSTRUCTION
 ACTIVITIES.
  
 11. TRASH AND DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 12. SUITABLE ACCESS SHALL BE PROVIDED DURING
 CONSTRUCTION ACTIVITIES.
  
 13. THE FIRE DEPARTMENT CONNECTION SHALL BE INSTALLED
 WITHIN 150 FEET OF A FIRE HYDRANT.
  
 14. EXITS SHALL MEET MINIMUM CODE REQUIREMENTS AND
 AFFORD THE REQUIRED PROTECTION AS STIPULATED IN CODE
 DOCUMENTS.
  
  
 MIKE CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE
 PHONE (561) 804-4707
 FAX (561) 804-4766