| 2011-10-05 17:29:25 | FORMAL SITE PLAN REVIEW CASE NO. 11-01 (Z11090018) |
| | FIRE STATION # 5 AND EMERGENCY OPERATIONS CENTER |
| | 700 NORTH CONGRESS AVENUE |
| | |
| | 1. ON COVER SHEET, PHILLIP T. WEBB IS LISTED AS FIRE |
| | CHIEF. CHIEF WEBB HAS RETIRED AND CARLOS S. CABRERA IS |
| | THE NEW FIRE CHIEF. |
| | |
| | 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 3. EXISTING FIRE STATION SHALL BE ABLE TO REMAIN IN |
| | FULL OPERATION DURING CONSTRUCTION ACTIVITIES OF NEW |
| | FACILITY. CONTRACTOR TO COORDINATE WITH FIRE RESCUE |
| | STAFF TO AVOID ANY POSSIBLE DISRUPTIONS. |
| | |
| | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR NEW |
| | UNDERGROUND FUEL DIESEL TANK. |
| | |
| | 5. SEPARATE PLANS AND PERMITS REQUIRED FOR THE LP GAS |
| | TANK SHOWN ON COVER SHEET II. |
| | |
| | 6. A PERMIT WILL BE REQUIRED FOR THE DEMOLITION OF THE |
| | EXISTING FIRE STATION AFTER THE NEW FACILITY IS |
| | INSPECTED, TESTED, AND APPROVED BY CITY OFFICIALS. |
| | |
| | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY SECURITY |
| | GATES AND FENCES. |
| | |
| | 8. THE BUILDING ADDRESS IS REQUIRED TO BE AFFIXED TO |
| | THE BUILDING. A MINIMUM OF AT LEAST 6" HIGH AND AT |
| | LEAST 1" WIDE NUMBERS ARE REQUIRED. |
| | |
| | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY |
| | GENERATOR SYSTEM RELOCATIONS. |
| | |
| | 10. PROPER COORDINATION IS EXPECTED DURING PHASE 1, |
| | PHASE 2, AND PHASE 3 OF CONSTRUCTION. |
| | |
| | 11. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOORS. |
| | |
| | 12. ALL NEW STAIRS AND RAMPS WILL REQUIRE HANDRAILS. |
| | |
| | 13. THE FIRE HYDRANT PROPOSED WITHIN THE ENCLOSED FIRE |
| | STATION PARKING LOT SHALL BE PROVIDED WITH A MINIMUM OF |
| | 7'-6" CLEARANCE TO THE FRONT AND SIDES AND AT LEAST 4' |
| | FEET TO THE REAR OF IT. |
| | |
| | 14. HOW DOES FIRE RESCUE STAFF ACCESS THROUGH THE GATES |
| | FROM CONGRESS AVENUE? |
| | |
| | 15. ELECTRIC IS TO BE PROVIDED AT THE FLAG POLE TO |
| | COMPLY WITH FLAG REGULATIONS IF FLAG IS TO REMAIN UP |
| | DURING NIGHT-TIME PERIODS. |
| | |
| | 16. PLEASE DO NOT PLAN ON PLANTING ANY FICUS TYPE |
| | HEDGES AT THE SITE AS THEY CREATE EXTENSIVE MAINTENANCE |
| | ISSUES. |
| | |
| | 17. PLEASE ENSURE THAT PROPER DRAINAGE IS PROVIDED FOR |
| | THE RETAINING WALL AREA. |
| | |
| | 18. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| | WALLS AND CEILINGS. |
| | |
| | 19. PLEASE PROVIDE A LIFE SAFETY PLAN. |
| | |
| | 20. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | HOOD,DUCT, AND FIRE SUPPRESSION SYSTEM PLANNED FOR THE |
| | KITCHEN. |
| | |
| | 21. PLEASE INDICATE ALL VERTICAL AND HORIZONTAL FIRE |
| | SEPARATIONS. |
| | |
| | 22. PLEASE PROVIDE A DOOR SCHEDULE INDICATING ALL FIRE |
| | RATED DOORS. |
| | |
| | 23. SMOKE DETECTORS ARE REQUIRED IN ALL AREAS WHERE |
| | SLEEPING ACTIVITIES OCCUR. |
| | |
| | 24. ALL DRIVING AND PARKING SURFACES ARE EXPECTED TO |
| | SUPPORT HEAVY LOADS OF FIRE, PARAMEDICAL, NEWS, AND |
| | DELIVERY VEHICLES. THIS INCLUDES THE OVERFLOW PARKING |
| | AREA AS WELL. AREAS SUBJECT TO THESE WEIGHT LOADS SHALL |
| | BE ABLE TO SUPPORT AT LEAST 32 TONS. |
| | |
| | 25. ALL FIRE RATED WALLS ARE TO BE PROPERLY LABELED AND |
| | IDENTIFIED. |
| | |
| | 26. ACCESS CONTROL SECURITY DEVICES ARE TO BE INSTALLED |
| | AT THIS FACILITY. |
| | |
| | 27. AN EMERGENCY COMMUNICATION SYSTEM IS ALSO EXPECTED |
| | TO BE INSTALLED AT THIS LOCATION. |
| | |
| | 28. A KNOX-BOX WILL BE REQUIRED FOR THIS FACILITY. |
| | |
| | 29. MORE DETAILS NEEDED ON PROPOSED 911 MEMORIAL |
| | PLANNED BY OTHERS. |
| | |
| | 30. EXIT STAIRS ARE TO BE RATED WITH AT LEAST ONE HOUR |
| | FIRE RATED CONSTRUCTION AND BE PROTECTED WITH AT LEAST |
| | 45 MINUTE OPENING PROTECTIVE DEVICES AND BE EQUIPPED |
| | WITH SELF-CLOSING DEVICES. |
| | |
| | 31. NEW STAIRS ARE TO COMPLY WITH NEW STAIR |
| | REQUIREMENTS. |
| | |
| | 32. THE INSTALLATION OF CONSTRUCTION FENCING SHALL NOT |
| | INTERFERE WITH THE USE OF THE EXISTING FIRE STATION OR |
| | WITH CITIZEN'S ACCESSING THE FACILITY OR ITS SERVICES. |
| | |
| | 33. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEM. THE FIRE ALARM SYSTEM |
| | IS TO BE MONITORED BY A LICENSED FIRE ALARM COMPANY |
| | APPROVED FOR CENTRAL STATION SERVICE. |
| | |
| | 34. EXIT SIGNS, EMERGENCY LIGHTS, AND PORTABLE FIRE |
| | EXTINGUISHERS ARE TO BE PROVIDED THROUGHOUT THE |
| | FACILITY. |
| | |
| | 35. CAREFUL COORDINATION IS TO OCCUR WITH REGARDS TO |
| | CONSTRUCTION AND PERMITTING IN PHASES. |
| | |
| | 37. LOCKS THAT REQUIRE A KEY FROM THIE INSIDE OF THE |
| | ROOM (EXIT DOOR) IS NOT PERMITTED. |
| | |
| | 38. PLEASE SUBMIT COMPLETE ARCHITECTURAL, MECHANICAL, |
| | ELECTRICAL, PLUMBING, FIRE SPRINKLER AND FIRE ALARM |
| | PLANS TO THE CONSTRUCTION SERVICES DEPARTMENT. |
| | |
| | 39. TAMPER SWITCHES, A CHAIN AND LOCK ARE REQUIRED ON |
| | THE FIRE LINE BACKFLOW DEVICE. |
| | |
| | 40. CAREFUL LOCATIONS OF ALL UNDERGROUND UTILITIES AND |
| | SERVICES WILL BE REQUIRED AS THE EXISTING FIRE STATION |
| | WILL REMAIN IN OPERATION. |
| | |
| | 41. COORDINATION IS TO OCCUR WITH REGARDS TO ANY |
| | TRAFFIC CONTROL DEVICES FOR THE FIRE STATION. |
| | |
| | 42. TO ENSURE TIMELY COMPLETION AND UNNECESSARY CHANGE |
| | ORDERS, EQUIPMENT PLACEMENT AND WIRING IS TO BE |
| | ADEQUATELY ANALYZED TO PREVENT AFTER CONSTRUCTION |
| | MISTAKES OR AFTERTHOUGHTS. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MICHAEL E. CARSILLO, INTERIM ASSISTANT FIRE CHIEF |
| | WEST PALM BEACH FIRE RESCUE |
| | (561) 804-4707 PHONE |