| 2011-05-26 09:20:58 | PLANNING BOARD CASE NO. 1445U (Z11050019) |
| | 4200 NORTH FLAGLER DRIVE |
| | |
| | |
| | 1. PLANS AND PERMITS REQUIRED FOR ALL NEW CONSTRUCTION, |
| | RENOVATION, AND DEMOLITION ACTIVITIES. |
| | |
| | 2. CONSTRUCTION, RENOVATION, AND DEMOLITION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 3. SUITABLE ACCESS ROADS ARE TO BE MAINTAINED FOR FIRE |
| | AND PARAMEDICAL ACCESS. |
| | |
| | 4. EXISTING FIRE HYDRANT ON SHEET C-3 APPEARS TO BE |
| | DIRECTLY IN FRONT OF EXIT STAIRS. |
| | |
| | 5. PLEASE EXPLAIN TYPE OF CONSTRUCTION FOR MARINE PODS. |
| | |
| | 6. PLEASE INDICATE WHAT WILL BE STORED IN THE MARINE |
| | PODS. |
| | |
| | 7. ARE THESE MARINE PODS TEMPORARY (90 DAYS OR LESS) OR |
| | ARE THEY GOING TO BE PERMANENT. |
| | |
| | 8. PROPER FIRE SEPARATIONS ARE REQUIRED BETWEEN THE |
| | STORAGE AND BUSINESS USES FOR THE STORAGE / |
| | ADMINISTRATIVE OFFICES |
| | |
| | 9. COMPLETE ARCHITECTURAL, MECHANICAL, ELECTRICAL, |
| | PLUMBING, FIRE SPRINKLER AND FIRE ALARM SYSTEMS WILL |
| | NEED TO BE SUBMITTED TO THE CONSTRUCTION SERVICES |
| | DEPARTMENT. |
| | |
| | 10. ANY EXIT STAIRS THAT ARE PLANNED TARE O COMPLY WITH |
| | THE MINIMUM REQUIREMENTS OF THE CHAPTER 7, OF THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 11. PLEASE ILLUSTRATE ALL EMERGENCY EQUIPMENT TO |
| | INCLUDE ILLUMINATED EXIT SIGNS, EMERGENCY LIGHTS, |
| | PORTABLE FIRE EXTINGUISHERS, AND EMERGENCY EXIT DOORS. |
| | |
| | 12. ALL DOORS WITH AN OCCUPANT LOAD OF 100 OR MORE |
| | PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE AND IF |
| | THEY ARE FIRE RATED DOORS THEY ARE TO BE EQUIPPED WITH |
| | FIRE EXIT HARDWARE. |
| | |
| | 13. SEPARATE PLANS AND PERMITS REQUIRED FOR HOOD DUCT |
| | AND FIRE SUPPRESSION SYSTEMS PLANNED FOR THE CAFETERIA |
| | BUILDING. |
| | |
| | 14. PLEASE PROVIDE LIFE SAFETY PLANS FOR ALL PROPOSED |
| | BUILDINGS. |
| | |
| | 15. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR |
| | LOCATIONS. |
| | |
| | 16. BUILDINGS ARE TO BE IDENTIFIED. ALL BUILDINGS ARE |
| | REQUIRED TO BE EQUIPPED WITH ADDRESSES. ADDRESSES SHALL |
| | BE A MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE. |
| | |
| | 17. PLEASE INDICATE OCCUPANT LOADS FOR EACH BUILDING |
| | AND DECLARE THEIR USES. |
| | |
| | 18. ARE ANY FIRE LANES PLANNED. SOME OF THE NEW |
| | BUILDINGS WILL MOST LIKELY NEED FIRE LANES. |
| | |
| | 19. PLEASE ILLUSTRATE ANY TEMPORARY STAGING AND |
| | CONSTRUCTION TRAILER LOCATIONS. |
| | |
| | 20. PLEASE PROVIDE ANY CONSTRUCTION PHASING PLANS IF IT |
| | BECOMES NECESSARY. |
| | |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| |