Plan Review Notes
Plan Review Notes For Project Z11050019
Project Number Z11050019
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2011-06-07 15:20:131. APPLICANT IS ADVISED TO SUBMIT FOR AN ENGINEERING
 SERVICES DEPARTMENT SITE DEVELOPMENT PERMIT AS SOON AS
 POSSIBLE. TECHNICAL COMMENTS WILL BE PROVIDED DURING
 THAT PROCESS.
 2. EXISTING OUTFALL DRAINAGE SYSTEM WILL REQUIRE
 CONVERSION TO THE NEW DRAINAGE SYSTEM. THIS INCLUDES
 EXISTING ONSITE SYSTEM REDIRECTION, CONTROL STRUCTURE
 PLACEMENT, AND OUTFALL EXTENSION IN FLAGLER DRIVE.
 3. ISOLATE AND REMOVE EXISTING ABANDONED WATER LINES
 ASSOCIATED WITH THE PARCEL.
 4. CONSULT WITH THE FIRE DEPARTMENT REVIEWER REGARDING
 AMPLE FIRE HYDRANT PLACEMENT.
  
  
 BRIAN R. MOREE
 ENGINEERING SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-494-1098 OFFICE
 561-644-7270 CELLULAR
 [email protected]
2011-05-31 14:36:22MIRANDA BEADLES REVIEWED FOR BRIAN COLLINS. NO COMMENTS
 REGARDING TRAFFIC AND CIRCULATION.