Plan Review Notes
Plan Review Notes For Project Z11050013
Project Number Z11050013
Review Stop Z
Sequence Number 1
Notes
Date Text
2011-06-07 20:01:26ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.07.2011
 PROJECT NO.: Z11050013
 CASE NO.: ZBA 3270A
 ADDRESS: 316 SOUTHERN BOULEVARD AND 4001 SOUTH OLIVE
 AVENUE
 APPLICANT/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: EXPANSION OF PREVIOUSLY-APPROVED CLASS
 B SPECIAL USE PERMIT FOR THE CONSTRUCTION OF A
 FULL-SERVICE CAR WASH FACILITY, INCORPORATING THE
 PROPERTY TO THE WEST INTO THE PROPOSED DEVELOPMENT.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. UPDATED APPLICATION SHALL BE PROVIDED SHOWING THE
 NEW AGENT AND ASSOCIATED CONTACT INFORMATION.
  
 2. UPDATED OWNER?S CONSENT FORM SHALL BE PROVIDED FOR
 THE NEW AGENT.
  
 3. UPDATED UTILITY LETTERS SHALL BE PROVIDED FROM THE
 FOLLOWING:
  
 A. CITY OF WEST PALM BEACH
 B. FLORIDA PUBLIC UTILITIES
 C. FLORIDA POWER & LIGHT
 D. COMCAST
 E. AT&T
  
 4. UPDATED TRAFFIC CONCURRENCY LETTER SHALL BE PROVIDED
 FROM PALM BEACH COUNTY TRAFFIC DIVISION.
  
 5. JUSTIFICATION STATEMENT INDICATES STORAGE OF
 EQUIPMENT AND PRODUCTS TO BE USED AT ?POTENTIAL FUTURE
 RUBBER DUCKY CAR WAS LOCATION.? PLEASE CLARIFY. THERE
 MAY BE SOME CONCERN THAT THIS FACILITY IS USED AS
 ?WAREHOUSING? FOR OTHER SITES.
  
 6. APPLICANT WILL NEED TO MEET WITH REPRESENTATIVES OF
 THE ADJACENT RESIDENTIAL NEIGHBORHOOD, AS WELL AS THE
 DISTRICT COMMISSIONER, PRIOR TO ANY PUBLIC HEARING.
  
 7. AN UPDATED LETTER SHALL BE PROVIDED FROM THE CITY?S
 SANITATION DEPARTMENT ACCEPTING THE PROPOSED SITE PLAN
 FOR USE OF A ROLL-OUT DUMPSTER WITHIN THE BUILDING. A
 DROP CURB WILL NEED TO BE PROVIDED TO ALLOW THE
 DUMPSTER TO BE MOVED FROM THE STORAGE ROOM.
  
 8. JUSTIFICATION LETTER INDICATES THAT 3 ANGLED SPACES,
 PLUS 1 HANDICAP SPACE, ARE BEING PROVIDED. THE PLANS
 INDICATE 4 ANGLED SPACES, PLUS 1 HANDICAP SPACE. PLEASE
 ADJUST THE JUSTIFICATION STATEMENT ACCORDINGLY.
  
 9. THE SURVEY INDICATES 2 A/C CONDENSING UNITS LOCATED
 ON THE WEST SIDE OF THE STRUCTURE. THESE UNITS CONFLICT
 WITH THE PROPOSED LANDSCAPING AND ARE NOT SHOWN ON THE
 SITE/LANDSCAPE PLANS. PLEASE CLARIFY AS TO WHETHER OR
 NOT THESE UNITS ARE BEING RELOCATED. IF THEY ARE TO
 REMAIN, PLEASE REVISE THE SITE AND LANDSCAPE PLANS TO
 SHOW THEIR LOCATION AND ADJUST THE PLANTINGS
 ACCORDINGLY.
  
 10. THE SURVEY SHOWS A COVERED WALKWAY ON THE EAST SIDE
 OF THE STRUCTURE. THIS IS NOT SHOWN ON THE
 SITE/LANDSCAPE PLANS. PLEASE CLARIFY AS TO WHETHER OR
 NOT THIS IS TO REMAIN OR BE REMOVED. IF IT IS TO
 REMAIN, THE 3RD PARKING SPACE SOUTH OF SOUTHERN
 BOULEVARD IS IN CONFLICT. ADJUST ALL PLANS ACCORDING TO
 WHAT IS PROPOSED FOR THE COVERED WALKWAY.
  
 11. CONSIDERATION SHOULD BE MADE TO ANGLE THE PARKING
 SPACES AT 90 DEGREES AND CONSOLIDATE THEM INTO ONE
 PARKING ROW (SEE SKETCH PROVIDED BY STAFF).
  
 12. A PARKING DETAIL SHALL BE PROVIDED SHOWING
 CONFORMANCE WITH THE CITY?S ZLDRS.
  
 13. PLEASE PROVIDE THE PROPOSED SETBACK FROM THE CANOPY
 TO THE SOUTH PROPERTY LINE.
  
 14. WHAT IS THE MINIMUM WIDTH NECESSARY FOR THE
 ?DETAIL? LANES? IS IT POSSIBLE TO GAIN SUFFICIENT SPACE
 TO INCLUDE A LANDSCAPE MEDIAN BETWEEN THE CANOPY AND
 THE THRU LANE? IF NOT, SOME TYPE OF DEVICE (I.E.
 BOLLARD) MAY NEED TO BE PROVIDED IN FRONT OF THE
 CANOPY?S SUPPORT POST TO PREVENT IT FROM BEING STRUCK
 BY VEHICLES.
  
 15. WRITTEN CONFIRMATION SHALL BE PROVIDED FROM THE
 CITY?S FIRE MARSHALL, OR DESIGNATED REPRESENTATIVE,
 INDICATING THAT THEY ARE ACCEPTING OF THE PROPOSED SITE
 PLAN WITH REGARDING TO CLEAR ACCESS, ETC.
  
 16. A CONCRETE PAD APPEARS TO BE SHOWN BETWEEN THE
 EXISTING BUILDING AND SOUTHERN BOULEVARD, BUT IT IS
 UNCLEAR AS TO ITS PURPOSE. IS THIS INTENDED FOR A BIKE
 RACK? IF SO, PLEASE INDICATE AS SUCH.
  
 17. THE SITE PLAN INDICATES THAT THE EXISTING BUILDING
 IS 1,690 SQUARE FEET; HOWEVER THE DIMENSIONS ON THE
 SURVEY RESULT IN A BUILDING IN EXCESS OF 1,723 SQUARE
 FEET. PLEASE VERIFY THE NUMBERS PROVIDED AND ADJUST
 ACCORDINGLY.
  
 18. PLEASE CLARIFY THE OPEN SPACE CALCULATION. DOES
 THIS FACTOR OUT THE CANOPY? IF SO, PLEASE NOTE THE
 SQUARE FOOTAGE OF THE CANOPY SOMEWHERE IN THE SITE DATA
 TABLE.
  
 19. PLEASE CLARIFY ?EXISTING? UNDER THE PERVIOUS AND
 IMPERVIOUS CALCULATIONS. AS THE SITE IS UNDER
 CONSTRUCTION, ETC. I WOULD SIMPLY INCLUDE ?REQUIRED?
 INSTEAD OF ?EXISTING?.
  
 20. PLEASE VERIFY THE ?BUILDING LOT COVERAGE?
 CALCULATION PROVIDED UNDER PERVIOUS. ADDING THE ?TOTAL
 BUILDING AREA? AND THE SIZE OF THE CANOPY RESULTS IN
 APPROXIMATELY 7,702 SQUARE FEET. PLEASE DOUBLE-CHECK
 ALL NUMBERS AND ADJUST ACCORDINGLY.
  
 21. THE FINAL ORDER FOR THE PREVIOUS CLASS B SPECIAL
 USE PERMIT PROVIDED A CONDITION THAT ?NO STORAGE OF
 VEHICLES SHALL BE PERMITTED ON-SITE. ALL SERVICES SHALL
 BE LIMITED TO ?WAITING CUSTOMERS? (I.E. NO DROP-OFF
 SERVICE).? THIS CONDITION WILL BE EXPANDED UPON TO
 INCLUDE SIGNAGE THAT MUST BE INSTALLED ON THE PROPERTY
 INDICATING SUCH. DETAILS ON THIS CONDITION WILL BE
 PROVIDED AS THE STAFF REPORT IS PREPARED.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  