2011-01-27 07:02:38INFORMAL SITE PLAN REVIEW 11-01 (Z11010003)
 NEW APARTMENT BUILDING
 TAMARIND AVENUE BETWEEN 15TH STREET AND GRANT STREET
  
  
 1. WRONG CODE EDITION ON SHEET A1.0. SHOULD READ ALL
 WORK TO COMPLY WITH THE FLORIDA FIRE PREVENTION CODE
 2007 EDITION (NFPA 1, 2006 EDITION AND NFPA 101 LIFE
 SAFETY CODE, 2006 EDITION.
  
 2. ELECTRIC POWERED SMOKE ALARMS ARE TO BE PROVIDED ON
 ALL LEVELS AND WITHIN EACH SLEEPING ROOM.
  
 3. BUILDING ADDRESS (ES) REQUIRED. A MINIMUM OF AT
 LEAST 6" HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED
 THAT CONTRAST TO THE BACKGROUND THEY ARE AFFIXED TO.
  
 4. THE BUILDING IS TO COMPLY WITH CHAPTER 30, NEW
 APARTMENT BUILDINGS PER NFPA 101 THE LIFE SAFETY CODE,
 2006 EDITION.
  
 5. PORTABLE FIRE EXTINGUISHERS WILL BE REQUIRED.
  
 6. EMERGENCY INSTRUCTIONS FOR RESIDENTS ARE TO BE
 PROVIDED ANNUALLY TO THE RESIDENTS.
  
 7. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS OF APARTMENT UNITS.
  
 8. PLEASE PROVIDE DETAILS ON STAIRS, HANDRAILS AND
 GUARDRAILS.
  
 9. PLEASE SUBMIT COMPLETE PLANS TO THE CONSTRUCTION
 SERVICES DEPARTMENT FOR REVIEW WHICH INCLUDES
 ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND
 FIRE SAFETY DETAIL DRAWINGS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION