Plan Review Notes
Plan Review Notes For Project Z10120012
Project Number Z10120012
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-01-07 17:23:11215 SOUTH OLIVE AVENUE AND 303 EVERNIA STREET
 CASE NUMBER Z10120012
  
 THESE COMMENTS ARE BASED UPON A SITE VISIT PERFORMED BY
 THE FIRE RESCUE DEPARTMENT ON DECEMBER 22, 2010 AND
 OTHER INFORMATION PROVIDED BY CITY STAFF.
  
 1. ON THE NORTH SIDE OF THE PROPERTY A PARTIALLY
 ENCLOSED EXIT STAIR EXISTS WHICH PROVIDES EXITING FROM
 A CONVERGENCE POINT BETWEEN THE TWO BUILDINGS. THIS
 EXIT STAIR APPEARS TO BE REQUIRED SINCE THE EXTERIOR
 FIRE ESCAPE AND EXIT DOORS FROM ONE BUILDING AND
 ANOTHER EXIT DOOR FROM THE OTHER BUILDING CAN LOAD TO
 THESE STAIRS FOR EXITING.
  
 2. IT APPEARS THAT BOTH BUILDINGS CONTAIN AUTOMATIC
 FIRE SPRINKLER SYSTEMS AND SEPARATE FIRE DEPARTMENT
 CONNECTIONS EXIST. IT HAS BEEN REPORTED BY CITY STAFF
 THAT A FIRE SPRINKLER SYSTEM MAY BE FED FROM A 3"
 UNDERGROUND FIRE MAIN THAT WAS INSTALLED SEVERAL
 DECADES AGO. IF A 3" UNDERGROUND LINE IS SUPPLYING
 WATER TO A FIRE SPRINKLER SYSTEM IT MUST BE DOCUMENTED
 AND PROVEN THAT THIS LINE CAN HYDRAULICALLY SUPPLY THE
 DEMANDS FOR THE FIRE SPRINKLER SYSTEM.
  
 3. IT APPEARS THAT SEPARATE FIRE ALARM SYSTEMS EXIST
 FOR EACH BUILDING.
  
 4. DURING THE SITE VISIT, CODE VIOLATIONS WERE
 DISCOVERED IN EACH BUILDING AND THE PROPERTY OWNER HAS
 RECEIVED WRITTEN NOTIFICATION FROM THIS OFFICE AND IT
 IS THE EXPECTATION THAT THESE CODE VIOLATIONS BE
 CORRECTED. THE SECOND FLOOR OF THE 303 EVERNIA STREET
 BUILDING WAS VACANT AT TIME OF THE FIRE RESCUE VISIT.
  
 5. THIS OFFICE CANNOT COMMENT CURRENTLY ON THE
 INDEPENDENCE OR SHARED MECHANICAL, ELECTRICAL, PLUMBING
 SYSTEMS FOR THE BUILDINGS.
  
 6. IT APPEARS THAT METAL INFRASTRUCTURE EXISTS BETWEEN
 THE TWO BUILDINGS THAT FORMS THE FRAMEWORK (PLATFORM,
 STAIRS,CONNECTION POINTS) THAT ESTABLISHES EXIT ACCESS
 FROM THE PREVIOUSLY DESCRIBED PARTIALLY ENCLOSED
 STAIRS. MAINTENANCE AND OVERSIGHT WILL BE NECESSARY TO
 ENSURE RELIABILITY OF THIS INFRASTRUCTURE.
  
 7. IT IS BELIEVED THAT NO BACKFLOW PREVENTION DEVICES
 EXIST FOR THE FIRE SPRINKLER SYSTEMS.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  