2011-01-12 11:15:48PLEASE RESPOND TO COMMENTS IN WRITTING:
  
 #1 OUR RECORDS SHOW THAT AT ONE TIME BUILDING HAD A 6"
 FIRE LINE, THEN IN 1954 IT WAS REDUCED TO 3". AFTER
 1954 THE BUILDING TO THE SOUTH MUST HAVE BEEN ADDED TO
 THE EXISTING SYSTEM, IT HAS SPRINKLER HEADS, BUT WE
 HAVE NO RECORD OF A SEPARATE FIRE LINE. WE HAVE NO
 RECORD OF THE SPRINKLER LINE BEING INCREASED TO 6", SO
 THERE ARE TWO PROPOSED PROPERTIES SERVED BY ONE 3" FIRE
 LINE. PLEASE SUPPLY INFORMATION HOW EACH BUILDING WILL
 BE SERVED.
  
 #2 THE ELECTRIC SERVICE TO THE SOUTH BUILDING CROSSES
 THIS PROPERTY FROM THE ALLEY, THEIR ELECTRIC METER IS
 ON THE WAGG BUILDING, BUT THE OVERHEAD CONDUITS TO THE
 ELECTRIC SERVICE GOES THRU THE AREA SHADED AND MARKED
 "50 X 11', FIRE ESCAPES THIS AREA". THE BUILDING TO THE
 SOUTH MUST HAVE A SANITARY LATERAL AND IT MUST COME
 THRU THIS "FIRE ESCAPE" AREA OR IT'S TIED TO THE WAGG
 BUILDING BECAUSE THERE IS NO SANITARY SEWER IN EVERNIA
 OR OLIVE THAT I AM AWARE OF.
  