| 2011-01-12 11:15:48 | PLEASE RESPOND TO COMMENTS IN WRITTING: |
| | |
| | #1 OUR RECORDS SHOW THAT AT ONE TIME BUILDING HAD A 6" |
| | FIRE LINE, THEN IN 1954 IT WAS REDUCED TO 3". AFTER |
| | 1954 THE BUILDING TO THE SOUTH MUST HAVE BEEN ADDED TO |
| | THE EXISTING SYSTEM, IT HAS SPRINKLER HEADS, BUT WE |
| | HAVE NO RECORD OF A SEPARATE FIRE LINE. WE HAVE NO |
| | RECORD OF THE SPRINKLER LINE BEING INCREASED TO 6", SO |
| | THERE ARE TWO PROPOSED PROPERTIES SERVED BY ONE 3" FIRE |
| | LINE. PLEASE SUPPLY INFORMATION HOW EACH BUILDING WILL |
| | BE SERVED. |
| | |
| | #2 THE ELECTRIC SERVICE TO THE SOUTH BUILDING CROSSES |
| | THIS PROPERTY FROM THE ALLEY, THEIR ELECTRIC METER IS |
| | ON THE WAGG BUILDING, BUT THE OVERHEAD CONDUITS TO THE |
| | ELECTRIC SERVICE GOES THRU THE AREA SHADED AND MARKED |
| | "50 X 11', FIRE ESCAPES THIS AREA". THE BUILDING TO THE |
| | SOUTH MUST HAVE A SANITARY LATERAL AND IT MUST COME |
| | THRU THIS "FIRE ESCAPE" AREA OR IT'S TIED TO THE WAGG |
| | BUILDING BECAUSE THERE IS NO SANITARY SEWER IN EVERNIA |
| | OR OLIVE THAT I AM AWARE OF. |
| | |
| | MANUEL JULIAN GONZALEZ |