| 2010-11-22 12:05:33 | INFORMAL SITE PLAN REVIEW |
| | 4215 UP THE GROVE LANE |
| | FLORIDA POWER AND LIGHT OFFICES AND EMERGENCY |
| | OPERATIONS CENTER |
| | |
| | 1. PROVISIONS ARE TO BE MADE FOR FIRE AND PARAMEDICAL |
| | ACCESS THROUGH THE ROLLING GATE. |
| | |
| | 2. THE FIRE HYDRANT NEAR THE BUILDING SHOULD BE |
| | RELOCATED AT LEAST 40 FEET AWAY FROM THE BUILDING. |
| | |
| | 3. THE FIRE LINE BACKFLOW PREVENTION DEVICE SHALL BE |
| | EQUIPPED WITH TAMPER SWITCHES, CHAIN AND LOCK. |
| | |
| | 4. A KNOX BOX WILL BE REQUIRED FOR THE BUILDING. KNOX |
| | LOCKING CAPS ARE REQUIRED FOR THE FIRE DEPARTMENT |
| | CONNECTION. THESE DEVICES CAN BE ORDERED AT |
| | WWW.KNOXBOX.COM. |
| | |
| | 5. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | GENERATOR INSTALLATION. |
| | |
| | 6. PLEASE CLASSIFY THE BUILDING AS AN ASSEMBLY |
| | OCCUPANCY NOT OFFICES AS DESCRIBED ON SHEET A-101. |
| | |
| | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEM. |
| | |
| | 8. PLEASE DECLARE ON DRAWINGS ALL EXIT FACILITIES. |
| | |
| | 9. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR LOCATIONS. |
| | |
| | 10. THE FIRE LINE INSTALLATION SHALL COMPLY WITH NFPA |
| | 24. THE FIRE LINE HAS A FIRE HYDRANT INSTALLED ON THE |
| | SAME LINE AS THE FIRE SPRINKLER SYSTEM. ALSO ON SHEET |
| | C1.0 A SIGNIFICANT AMOUNT OF PIPE IS SHOWN FOR THE FDC. |
| | IT IS NOT NECESSARY TO INSTALL THIS AMOUNT OF PIPE. THE |
| | FDC CAN BE INSTALLED NEARER THE BUILDING. ALSO PLEASE |
| | EXPLAIN THE 200 PSI ABOVE GROUND CHECK VALVE ON THE |
| | FIRE LINE ON C1.0. THIS ARRANGEMENT DOES NOT APPEAR TO |
| | BE NORMAL. |
| | |
| | 11. PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR |
| | WALLS AND CEILINGS. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | (561) 804-4724 PHONE |
| | (561) 804-4774 FAX |
| | [email protected] |
| |