Plan Review Notes
Plan Review Notes For Project Z10110006
Project Number Z10110006
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-11-22 12:05:33INFORMAL SITE PLAN REVIEW
 4215 UP THE GROVE LANE
 FLORIDA POWER AND LIGHT OFFICES AND EMERGENCY
 OPERATIONS CENTER
  
 1. PROVISIONS ARE TO BE MADE FOR FIRE AND PARAMEDICAL
 ACCESS THROUGH THE ROLLING GATE.
  
 2. THE FIRE HYDRANT NEAR THE BUILDING SHOULD BE
 RELOCATED AT LEAST 40 FEET AWAY FROM THE BUILDING.
  
 3. THE FIRE LINE BACKFLOW PREVENTION DEVICE SHALL BE
 EQUIPPED WITH TAMPER SWITCHES, CHAIN AND LOCK.
  
 4. A KNOX BOX WILL BE REQUIRED FOR THE BUILDING. KNOX
 LOCKING CAPS ARE REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTION. THESE DEVICES CAN BE ORDERED AT
 WWW.KNOXBOX.COM.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 GENERATOR INSTALLATION.
  
 6. PLEASE CLASSIFY THE BUILDING AS AN ASSEMBLY
 OCCUPANCY NOT OFFICES AS DESCRIBED ON SHEET A-101.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEM.
  
 8. PLEASE DECLARE ON DRAWINGS ALL EXIT FACILITIES.
  
 9. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR LOCATIONS.
  
 10. THE FIRE LINE INSTALLATION SHALL COMPLY WITH NFPA
 24. THE FIRE LINE HAS A FIRE HYDRANT INSTALLED ON THE
 SAME LINE AS THE FIRE SPRINKLER SYSTEM. ALSO ON SHEET
 C1.0 A SIGNIFICANT AMOUNT OF PIPE IS SHOWN FOR THE FDC.
 IT IS NOT NECESSARY TO INSTALL THIS AMOUNT OF PIPE. THE
 FDC CAN BE INSTALLED NEARER THE BUILDING. ALSO PLEASE
 EXPLAIN THE 200 PSI ABOVE GROUND CHECK VALVE ON THE
 FIRE LINE ON C1.0. THIS ARRANGEMENT DOES NOT APPEAR TO
 BE NORMAL.
  
 11. PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
 [email protected]