Plan Review Notes
Plan Review Notes For Project Z10090014
Project Number Z10090014
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-09-30 09:05:06PLANNING BOARD CASE NO. 1603 (Z10090014)
 2101 PALM BEACH LAKES BOULEVARD
  
 1. NEW BUILDING SHALL MEET THE REQUIREMENTS FOR A CLASS
 A MERCANTILE OCCUPANCY.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS.
  
 3. WHAT FIRE RATING DOES THE DOORS HAVE LOCATED WITHIN
 THE 4 HOUR FIRE WALL.
  
 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 5. PROPER EXITS ARE TO BE PROVIDED FROM THIS CLASS A
 MERCANTILE OCCUPANCY.
  
 6. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A THIRD
 PARTY CERTIFICATED APPROVED MONITORING COMPANY FOR
 CENTRAL STATION SERVICE.
  
 7. KNOX LOCKING CAPS ARE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION.
  
 8. THE FIRE DEPARTMENT CONNECTION SHALL BE LOCATED NO
 FATHER THAN 150 FEET FROM A FIRE HYDRANT.
  
 9. BUILDING ADDRESS IS REQUIRED. THE MINIMUM HEIGHT OF
 THESE NUMBERS ARE TO BE 6" AND AT LEAST 1" WIDE.
  
 10. SINCE THIS BUILDING IS SEPARATE FROM THE OTHER ONE,
 SEPARATE UTILITIES AND INFRASTRUCTURE IS EXPECTED.
  
 11. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 12. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 13. PLEASE ILLUSTRATE THE LOCATIONS OF ALL EMERGENCY
 LIGHTS AND EXIT SIGNS.
  
 14. PLEASE ILLUSTRATE THE LOCATIONS OF ALL PORTABLE
 FIRE EXTINGUISHERS.
  
 15. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 16. PLEASE ILLUSTRATE ON THE PLANS THE 60" AISLE THAT
 IS REQUIRED TO REACH AN EXIT.
  
 17. PLEASE SUBMIT COMPLETE ARCHITECTURAL, MECHANICAL,
 ELECTRICAL, PLUMBING, FIRE SPRINKLER AND FIRE ALARM
 PLANS TO THE CONSTRUCTION SERVICES DEPARTMENT.
  
 18. PLEASE SUBMIT A LIFE SAFETY PLAN.
  
 19. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING,
 AND AFTER CONSTRUCTION.
  
 20. KNOX-BOX MATERIALS CAN BE ORDERED AT
 WWW.KNOX-BOX.COM.
  
 21. AN EMERGENCY PLAN AND STAFF TRAINING FOR EMERGENCY
 EGRESS AND THE USE OF PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 22. FIRE DRILLS ARE REQUIRED IN CLASS A AND B
 MERCANTILE OCCUPANCIES.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX