| Plan Review Notes For Project Z10090014 |
| Project Number |
Z10090014 |
|
| Review Stop |
ENG - PPRC |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-12 10:05:14 | 1. (SHEET C1) FINISHED FLOOR ELEVATION (FFE) IS LOWER | | | THAN NEARBY EXISTING SEWER MANHOLE. FFE SHOULD BE A | | | MINIMUM 12??? ABOVE ADJACENT ROADWAY / PARKING AREA | | | ELEVATION. | | | 2. (SHEET A1.2) HANDICAPPED RAMPS AND ACCESS ROUTES | | | SHALL HAVE DETECTABLE WARNING THAT COMPLIES WITH FBC | | | 11-4.29. PREFABRICATED ANSI A117.1-1986 TRUNCATED DOMES | | | ARE PREFERRED. | | | 3. (SHEET LA-2) LANDSCAPE MATERIAL PLANTING LOCATION | | | CONFLICTS WITH EXISTING BACKFLOW PREVENTER. | | | 4. (SHEET LA-2) PROPOSED DUMPSTER LOCATION CONFLICTS | | | WITH EXISTING SEWER MANHOLE. | | | 5. PRIVATE FIRE LINE / FDC IN SOUTHEAST CORNER OF | | | PROPERTY IS IN CONFLICT WITH PROPOSED DRIVEWAY | | | ENTRANCE. ONE OF THE TWO ELEMENTS WILL NEED TO BE | | | RELOCATED. | | | 6. UNITY OF TITLE APPLICATION REQUIRED. ( BUILDING | | | CONNECTION AND SHARED INFRASTRUCTURE.) | | | 7. PERVIOUS AND IMPERVIOUS CALCULATIONS REQUIRED. | | | 8. WATER/ SEWER / FIRE SYSTEM DESIGN CALCULATIONS | | | REQUIRED. | | | 9. SHOW ALL FDC AND HYDRANT LOCATIONS. | | | | | | BRIAN R. MOREE | | | ENGINEERING SERVICES DEPARTMENT | | | 561-644-7270 | | | | | | |
| |