| Date |
Text |
| 2010-06-04 16:42:56 | FAILED |
| | |
| | NO OBJECTION TO PROPOSED ABANDONMENT OF RIGHT-OF-WAY |
| | (ROW) AT COCOANUT & TUXEDO (SEE MASTER PLAN SHEET 1) |
| | FOR NEW ROAD SECTION. HOWEVER, UTILITY EASEMENTS SHALL |
| | REMAIN UNCHANGED AS THEY RELATE TO THIS ABANDONED |
| | PORTION OF THE ROW AT THIS INTERSECTION. |
| | |
| | DUMPSTER ENCLOSURE LOCATION PROPOSED WILL NOT BE |
| | SERVICEABLE BY SANITATION TRUCK FOR SOLID WASTE PICK |
| | UP. SEE AUTO TURN ANALYSIS PLAN/ SHEET: NOTE THE |
| | DIMENSIONS OF THE FIRE TRUCK SHOWN ARE SIMILAR TO THAT |
| | OF A FRONT LOADER SANITATION TRUCK THUS; THE TURN |
| | RADIUS IS TOO SMALL. THIS LOCATION WAS USED AT SOME |
| | TIME IN THE PAST FOR TRASH PICK UP (WITHOUT AN |
| | ENCLOSURE), BUT WAS MOVED TO THE S.W. AREA BEHIND THE |
| | EXISTING MAIN BUILDING ON FLAGLER BECAUSE OF THE |
| | DIFFICULTY OF KEEPING THE TRUCK OFF OF THE GRASS |
| | PLAYFIELD. |
| | |
| | A NEW LOCATION FOR THE DUMPSTER ENCLOSURE IS SUGGESTED |
| | IN THE CURRENT AREA OF PICK UP WITH A 12 FT. 6 INCH |
| | MAIN OPENING FOR SERVICE ACCESS. THE REMAINING 3.5 FT. |
| | FOR A RECYCLE BINS AREA CAN BE CONFIGURED ADJACENT TO |
| | THE ENCLOSURE IN A MANOR WITH THE DOORS OPENINGS AT THE |
| | WIDER SIDE (OF THE FRONT LEFT SIDE) TO SAVE ROOM. ALSO, |
| | PLEASE SHOW WHERE THE OVER-HANG OF THE PROPOSED COVERED |
| | PICK UP/DROP OFF AREAS WILL BE ON THE PLANS. |
| | |
| | PREFER TO TAP FIRE HYDRANTS AND POTABLE WATER SERVICES |
| | SEPARATELY TO THE WATER MAIN RATHER THAN TEEING THE |
| | HYDRANT OFF OF THE POTABLE WATER LINE CONNECTION. |
| | PLEASE PROVIDE JUSTIFICATION AND PRESSURE CALCULATIONS |
| | FOR RATIONALE FOR THIS CONNECTION TYPE. |
| | |
| | IF I MAY BE OF FURTHER ASSISTANCE: |
| | |
| | EMERY P. FABIAN |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 561-822-1200 |
| | FAX: 561-494-1116 |
| | MOBILE: 561-662-2269 |
| | EMAIL: [email protected] |
| | |
| |