| 2010-05-28 11:29:32 | PLANNING BOARD CASE # 1601 |
| | 1101-54TH STREET |
| | Z10050019 |
| | |
| | |
| | 1. WRONG FIRE DEPARTMENT LISTED ON COVER PAGE. WEST |
| | PALM BEACH FIRE RESCUE STATION # 3 IS LOCATED AT 5050 |
| | BROADWAY NOT PALM BEACH COUNTY FIRE RESCUE. |
| | |
| | 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| | |
| | 3. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 4. THE EXISTING FIRE ALARM SYSTEM, FIRE SPRINKLER |
| | SYSTEM, FIRE PUMP, HOOD EXTINGUISHING SYSTEM, EMERGENCY |
| | LIGHTING, EXIT DOORS, AND SIMILAR ITEMS SHALL BE |
| | INSPECTED BY LICENSED CERTIFIED CONTRACTORS TO ENSURE |
| | PROPER OPERATION. |
| | |
| | 5. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR HANDRAILS AND GUARDRAILS. |
| | |
| | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY |
| | MODIFICATIONS TO ANY SAFETY SYSTEMS. |
| | |
| | 7. WRONG LIFE SAFETY CODE LISTED ON PAGE A-1 PROPOSED. |
| | SHOULD READ 2006 EDITION NOT 2003 EDITION. |
| | |
| | 8. SEPARATE PLANS AND PERMITS REQUIRED FOR PHASE II |
| | CONSTRUCTION. |
| | |
| | 9. PLEASE PROVIDE FIRESTOPPING DETAILS ON PLANS. |
| | |
| | 10. PLEASE PROVIDE DOOR SCHEDULE. |
| | |
| | 11. PLEASE PROVIDE DETAILS ON LIQUID PETROLEUM BOXES |
| | DISPLAYED ON BOUNDARY SURVEY. |
| | |
| | 12. THE PROPOSED FIRE HYDRANT SHALL BE INSTALLED, |
| | INSPECTED, TESTED, AND APPROVED PRIOR TO OCCUPANCY. |
| | |
| | 13. FIRE LANES NOT DISPLAYED ON PAGE SP.1. PLEASE |
| | ILLUSTRATE FIRE LANE LOCATIONS. |
| | |
| | 14. A KNOX BOX WILL BE REQUIRED. PLEASE SEE |
| | WWW.KNOXBOX.COM. |
| | |
| | 15. PLEASE ILLUSTRATE ALL EXISTING FIRE WALLS AND SMOKE |
| | BARRIERS. |
| | |
| | 16. PLEASE ILLUSTRATE ALL PORTABLE FIRE EXTINGUISHER |
| | LOCATIONS. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | (561) 804-4724 PHONE |
| | (561) 804-4774 FAX |
| | |
| | |
| | |
| |