Plan Review Notes
Plan Review Notes For Project Z10050019
Project Number Z10050019
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-05-28 11:29:32PLANNING BOARD CASE # 1601
 1101-54TH STREET
 Z10050019
  
  
 1. WRONG FIRE DEPARTMENT LISTED ON COVER PAGE. WEST
 PALM BEACH FIRE RESCUE STATION # 3 IS LOCATED AT 5050
 BROADWAY NOT PALM BEACH COUNTY FIRE RESCUE.
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 4. THE EXISTING FIRE ALARM SYSTEM, FIRE SPRINKLER
 SYSTEM, FIRE PUMP, HOOD EXTINGUISHING SYSTEM, EMERGENCY
 LIGHTING, EXIT DOORS, AND SIMILAR ITEMS SHALL BE
 INSPECTED BY LICENSED CERTIFIED CONTRACTORS TO ENSURE
 PROPER OPERATION.
  
 5. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY
 MODIFICATIONS TO ANY SAFETY SYSTEMS.
  
 7. WRONG LIFE SAFETY CODE LISTED ON PAGE A-1 PROPOSED.
 SHOULD READ 2006 EDITION NOT 2003 EDITION.
  
 8. SEPARATE PLANS AND PERMITS REQUIRED FOR PHASE II
 CONSTRUCTION.
  
 9. PLEASE PROVIDE FIRESTOPPING DETAILS ON PLANS.
  
 10. PLEASE PROVIDE DOOR SCHEDULE.
  
 11. PLEASE PROVIDE DETAILS ON LIQUID PETROLEUM BOXES
 DISPLAYED ON BOUNDARY SURVEY.
  
 12. THE PROPOSED FIRE HYDRANT SHALL BE INSTALLED,
 INSPECTED, TESTED, AND APPROVED PRIOR TO OCCUPANCY.
  
 13. FIRE LANES NOT DISPLAYED ON PAGE SP.1. PLEASE
 ILLUSTRATE FIRE LANE LOCATIONS.
  
 14. A KNOX BOX WILL BE REQUIRED. PLEASE SEE
 WWW.KNOXBOX.COM.
  
 15. PLEASE ILLUSTRATE ALL EXISTING FIRE WALLS AND SMOKE
 BARRIERS.
  
 16. PLEASE ILLUSTRATE ALL PORTABLE FIRE EXTINGUISHER
 LOCATIONS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  
  
  