| Notes |
| Date |
Text |
| 2010-05-28 12:29:27 | PLANNING BOARD CASE 1217I Z10050016 AND Z10050017 | | | CATALINA MAJOR PD AMENDMENT | | | | | | 1. A KNOX-BOX KEY SWITCH IS REQUIRED TO OPERATE THE | | | ENTRY GATE. THIS DEVICE CAN BE ORDERED AT KNOXBOX.COM. | | | | | | 2. BUILDING ADDRESSES ARE REQUIRED ON PROPER ELEVATION. | | | A MINIMUM OF AT LEAST 6" AND AT LEAST 1" WIDE NUMBERS | | | ARE REQUIRED. | | | | | | 3. ALL THREE STORY BUILDINGS ARE REQUIRED TO BE FIRE | | | SPRINKLER PROTECTED IN ACCORDANCE WITH FS 553.895 (2) | | | | | | 4. NO FIRE HYDRANTS DISPLAYED ON THE DRAWINGS. PLEASE | | | ILLUSTRATE ALL NEW AND EXISTING FIRE HYDRANTS. | | | | | | 5. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO | | | COMPLY WITH NFPA 241. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4724 PHONE | | | (561) 804-4774 FAX |
| |