| Plan Review Notes For Project Z10040024 |
| Project Number |
Z10040024 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-28 16:00:54 | PAL EXTENSION | | | 922-7TH STREET | | | FORMAL SITE PLAN REVIEW NO. 10-03 (Z10040024) | | | | | | | | | 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 3. PLEASE DECLARE CONSTRUCTION TYPE FOR ADDITION. | | | | | | 4. PLEASE DECLARE ON THE PLANS THE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 5. PLEASE ILLUSTRATE ALL ILLUMINATED EXIT SIGNS AND | | | EMERGENCY LIGHTS. | | | | | | 6. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 7. PLEASE INDICATE THE TYPES OF COOKING THAT IS PLANNED | | | FOR THE BREAKROOM. | | | | | | 8. PLEASE INDICATE ALL APPROPRIATE CODES FOR THE | | | PROJECT. | | | | | | 9. PLEASE SUBMIT COMPLETE STRUCTURAL, MECHANICAL, | | | ELECTRICAL, AND PLUMBING PLANS FOR REVIEW. | | | | | | 10. PLEASE SUBMIT A LIFE SAFETY PLAN FOR REVIEW. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4709 PHONE | | | (561) 804-4774 FAX | | | | | | | | | |
| |