Plan Review Notes
Plan Review Notes For Project Z10030022
Project Number Z10030022
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-03-25 08:45:411. ON PAGE C-2 THE PROPOSED FIRE LINE SIZES ARE NOT
 CALLED OUT.
  
 2. ON PAGE C-2 ONE FIRE HYDRANT NOT CALLED OUT.
  
 3. NO PARKING FIRE LANE AREAS NEED TO BE IDENTIFIED FOR
 THE SPECIAL CARE FACILITY. THESE AREAS ARE TO BE
 PROPERLY MARKED WITH PAVEMENT MARKINGS AND SIGNAGE.
  
 4. THE ENTIRE BUILDING WILL BE REQUIRED TO BE
 COMPLETELY FIRE SPRINKLER PROTECTED. QUICK RESPONSE
 SPRINKLER HEADS WILL BE REQUIRED. SEPARATE PLANS AND
 PERMITS WILL BE REQUIRED.
  
 5. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 6. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 7. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 8. A KNOX-BOX WILL BE REQUIRED.
  
 9. KNOX-BOX LOCKING CAPS WILL BE REQUIRED.
  
 10. THE BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT
 LEAST 6" HIGH AND AT LEAST 1" WIDE NUMBERS ARE
 REQUIRED.
  
 11. MORE DETAILS NEEDED FOR THE NOURISHMENT AREAS.
  
 12. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 13. SEPARATE PLANS AND PERMITS REQUIRED FOR EMERGENCY
 GENERATOR.
  
 14. STAIRWAY MARKINGS ARE REQUIRED.
  
 15. A BI-DIRECTIONAL AMPLIFIER WILL BE REQUIRED TO
 MAINTAIN MINIMUM RADIO STRENGTH FOR THE FIRE RESCUE
 DEPARTMENT.
  
 16. PLEASE ILLUSTRATE ALL FIRE AND SMOKE RATINGS BOTH
 HORIZONTALLY AND VERTICALLY.
  
 17. PLEASE ILLUSTRATE ALL FIRE RATED DOORS.
  
 18. ALL FIRE RATED WALLS SHALL BE PROPERLY IDENTIFIED
 AND ALL OPENINGS ARE TO BE PROTECTED.
  
 19. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF A COMPLETE FIRE ALARM SYSTEM. THE FIRE
 ALARM SYSTEM SHALL BE MONITORED BY A THIRD-PARTY
 APPROVED FOR MONITORING FIR CENTRAL STATION SERVICE.
  
 20. THE PORTA CACHERE SHALL BE A MINIMUM OF 13'-6"
 HIGH.
  
 21. ELEVATOR WARNINGS SIGNS REQUIRED AT ELEVATOR
 LOBBIES.
  
 22. PLEASE PROVIDE A DOOR SCHEDULE.
  
 23. PLEASE DECLARE CONSTRUCTION FOR FOR ANY LOGGIA'S OR
 WALKWAYS.
  
 24. PLEASE PROVIDE A PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 25. THE PROPOSED AUTO-TURN DRAWING IS DIFFICULT TO READ
 AND UNDERSTAND.
  
 26. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 GENERATOR.
  
 27. SUBMIT COMPLETE ARCHITECTURAL, MECHANICAL,
 ELECTRICAL, PLUMBING, FIRE ALARM AND FIRE SPRINKLER
 SYSTEM PLANS.
  
 28. AN EMERGENCY EVACUATION PLANS WILL BE REQUIRED FOR
 THE PROPERTY PRIOR TO OCCUPANCY. THIS PLAN MUST BE
 REVIEWED BY THIS OFFICE.
  
  
 DENIED
  
  