| Date |
Text |
| 2010-03-25 08:45:41 | 1. ON PAGE C-2 THE PROPOSED FIRE LINE SIZES ARE NOT |
| | CALLED OUT. |
| | |
| | 2. ON PAGE C-2 ONE FIRE HYDRANT NOT CALLED OUT. |
| | |
| | 3. NO PARKING FIRE LANE AREAS NEED TO BE IDENTIFIED FOR |
| | THE SPECIAL CARE FACILITY. THESE AREAS ARE TO BE |
| | PROPERLY MARKED WITH PAVEMENT MARKINGS AND SIGNAGE. |
| | |
| | 4. THE ENTIRE BUILDING WILL BE REQUIRED TO BE |
| | COMPLETELY FIRE SPRINKLER PROTECTED. QUICK RESPONSE |
| | SPRINKLER HEADS WILL BE REQUIRED. SEPARATE PLANS AND |
| | PERMITS WILL BE REQUIRED. |
| | |
| | 5. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 6. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| | |
| | 7. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | |
| | 8. A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 9. KNOX-BOX LOCKING CAPS WILL BE REQUIRED. |
| | |
| | 10. THE BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT |
| | LEAST 6" HIGH AND AT LEAST 1" WIDE NUMBERS ARE |
| | REQUIRED. |
| | |
| | 11. MORE DETAILS NEEDED FOR THE NOURISHMENT AREAS. |
| | |
| | 12. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. |
| | |
| | 13. SEPARATE PLANS AND PERMITS REQUIRED FOR EMERGENCY |
| | GENERATOR. |
| | |
| | 14. STAIRWAY MARKINGS ARE REQUIRED. |
| | |
| | 15. A BI-DIRECTIONAL AMPLIFIER WILL BE REQUIRED TO |
| | MAINTAIN MINIMUM RADIO STRENGTH FOR THE FIRE RESCUE |
| | DEPARTMENT. |
| | |
| | 16. PLEASE ILLUSTRATE ALL FIRE AND SMOKE RATINGS BOTH |
| | HORIZONTALLY AND VERTICALLY. |
| | |
| | 17. PLEASE ILLUSTRATE ALL FIRE RATED DOORS. |
| | |
| | 18. ALL FIRE RATED WALLS SHALL BE PROPERLY IDENTIFIED |
| | AND ALL OPENINGS ARE TO BE PROTECTED. |
| | |
| | 19. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | INSTALLATION OF A COMPLETE FIRE ALARM SYSTEM. THE FIRE |
| | ALARM SYSTEM SHALL BE MONITORED BY A THIRD-PARTY |
| | APPROVED FOR MONITORING FIR CENTRAL STATION SERVICE. |
| | |
| | 20. THE PORTA CACHERE SHALL BE A MINIMUM OF 13'-6" |
| | HIGH. |
| | |
| | 21. ELEVATOR WARNINGS SIGNS REQUIRED AT ELEVATOR |
| | LOBBIES. |
| | |
| | 22. PLEASE PROVIDE A DOOR SCHEDULE. |
| | |
| | 23. PLEASE DECLARE CONSTRUCTION FOR FOR ANY LOGGIA'S OR |
| | WALKWAYS. |
| | |
| | 24. PLEASE PROVIDE A PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR ALL HANDRAILS AND GUARDRAILS. |
| | |
| | 25. THE PROPOSED AUTO-TURN DRAWING IS DIFFICULT TO READ |
| | AND UNDERSTAND. |
| | |
| | 26. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | GENERATOR. |
| | |
| | 27. SUBMIT COMPLETE ARCHITECTURAL, MECHANICAL, |
| | ELECTRICAL, PLUMBING, FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEM PLANS. |
| | |
| | 28. AN EMERGENCY EVACUATION PLANS WILL BE REQUIRED FOR |
| | THE PROPERTY PRIOR TO OCCUPANCY. THIS PLAN MUST BE |
| | REVIEWED BY THIS OFFICE. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | WEST PALM BEACH FIRE RESCUE |
| | 500 NORTH DIXIE HIGHWAY |
| | WEST PALM BEACH, FLORIDA 33401 |
| | (561) 804-4724 PHONE |
| | (561) 804-4774 FAX |
| | MCARSILLO@WPB,ORG |
| |
Print |