Plan Review Notes
Plan Review Notes For Project Z10010005
Project Number Z10010005
Review Stop Z
Sequence Number 1
Notes
Date Text
2010-02-09 16:41:25REQUIREMENTS:
  
 SHOW SITE LIGHTING ON THE SITE PLAN AND LANDSCAPE PLAN.
  
 SHOW AREAS OF GATE SWINGS AND SLIDES ON THE LANDSCAPE
 PLAN TO ENSURE THAT GATE OPERATION WILL NOT INTERFERE
 WITH THE GATES.
  
 PLEASE PROVIDE A PHOTOMETRIC PLAN.
  
 SURVEY SHOULD BE UPDATED TO REFLECT THE UNITY OF TITLE
 ON THE SUBJECT PROPERTY (ORB 23043/1068).
  
 THE MINIMUML ANDSCAPE AREA IS 15 PERCENT, THE PLANS
 SHOW THE PROPOSED PERVIOUS AREA AS 11.9 PERCENT. PLEASE
 ADD MORE PERVIOUS AREA. SEE SECTION 94-145(5)(B).
  
 PROVIDE THE NORTH AND WEST ELEVATIONS OF THE PROPOSED
 BUILDING, ONLY THE SOUTH AND EAST ELEVATIONS WERE
 PROVIDED.
  
 PROVIDE ELEVATIONS OF THE DUMPSER ENCLOSURE
  
 PROVIDE FENCE AND GATE ELEVATIONS.
  
 PROVIDE CAR WASH ELEVATIONS.
  
 PROVIDE CALCULATIONS RELATING TO THE MINIMUM 30 PERCENT
 FOUNDATION PLANTING. SEE SECTION 94-443(E)(1).
  
 FAR IS BASED UPON TOTAL BUILDING SQUARE FOOTAGE
 EXCLUDING PARKING GARAGES AND EXTERIOR SPACE. THE SITE
 DATA APPEARS TO BE USING THE BUILDING FOOTPRINT AS THE
 BASIS FOR CALCULATING THE FAR, THIS IS INCORRECT AS THE
 SECOND FLOOR AND MEZZANINE SPACES SHOULD BE INCLUDED IN
 THE SQUARE FOOTAGE USED TO CALCULATE THE FAR.
  
 PLEASE ITEMIZE WHAT THE 31,696 SF OF ENCLOSED AREA IN
 THE PARKING CALCULATIONS INCLUDES. ITEMIZE BAY
 CALCULATIONS AS WELL. ALSO, IT APPEARS THAT THE 4 PREP
 AND 3 PAINT BOOTH BAYS IN THE BODY PAINT SHOP WERE NOT
 COUNTED.
  
 THE SQUARE FOOTAGES LISTED IN THE SPACES ON THE SITE
 PLAN DO NOT MATCH THE CORRESPONDING ENTRY ON THE SITE &
 BUILDING DATA TABLE. PLEASE CORRECT.
  
 PLEASE RELABEL THE "BAR" IN THE AUDI SHOWROOM TO
 "COFFEE BAR" OR SOMETHING SIMILAR.
  
 SUGGESTIONS/QUESTIONS:
  
 ADD A PEDESTRIAN DOOR TO THE DUMPSTER ENCLOSURE TO IT
 MAY BE ACCESSED WITHOUT THE NEED TO OPEN UP THE LARGE
 DOORS. THIS WILL HOPEFULLY REDUCE THE CHANCES OF THE
 DOORS BEING LEFT OPEN.
  
 RELOCATE THE CARWASH SOUTH SO IT IS DIRECTLY AGAINST
 THE RAMP. THE CURRENT PROPOSAL CREATES A 7 FOOT WIDE
 NO-MANS-LAND WHICH SERVES NO PURPOSE. THAT SPACE COULD
 BE MORE USEFUL TO BUFFER THE NORTH SIDE OF THE CARWASH.
  
 WILL THE COMPRESSORS BE HOUSED IN AN UNROOFED OR ROOFED
 STRUCTURE?
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 WITH QUESTIONS.
  
  
  
  