Plan Review Notes
Plan Review Notes For Project Z10010005
Project Number Z10010005
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-02-01 07:30:391. THE PAINT SPRAY BOOTHS SHALL COMPLY WITH NFPA 33,
 THE STANDARD FOR THE APPLICATION OF SPRAY MATERIALS.
  
 2. THE PROPOSED SPRAY BOOTHS SHALL BE EQUIPPED WITH
 AUTOMATIC FIRE SUPPRESSION EQUIPMENT. SEPARATE PLANS
 AND PERMITS REQUIRED FOR THE FIRE SUPPRESSION
 EQUIPMENT.
  
 3. PROPER MECHANICAL, ELECTRICAL SYSTEMS AND EQUIPMENT
 SHALL BE PROVIDED FOR THE SPRAY BOOTHS. APPROPRIATE
 PLANS AND PERMITS REQUIRED.
  
 4. THE STORAGE AND HANDLING OF FLAMMABLE AND
 COMBUSTIBLE LIQUIDS SHALL COMPLY WITH NFPA 30, THE
 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.
  
 5. PLEASE PROVIDE INFORMATION ON EXISTING FIRE SAFETY
 EQUIPMENT CONTAINED WITHIN THE AREA.
  
 6. PLEASE PROVIDE APPROPRIATE CUT SHEETS FOR PROPOSED
 SPRAY BOOTHS.
  
 7. PLEASE PROVIDE DETAILS ON FILTERS PLANNED TO BE USED
 FOR THE SPRAY BOOTHS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]