Plan Review Notes
Plan Review Notes For Project Z09110003
Project Number Z09110003
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-12-01 15:15:04 
 1. THE NEW ADDITION SHALL BE DESIGNED AND CONSTRUCTED
 TO FLORIDA BUILDING CODE 2007 AND THE FLORIDA FIRE
 PREVENTION CODE 2007 EDITION.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 3. COULD LOCATE ONLY ONE PROPOSED FIRE HYDRANT ON THE
 WATER AND WASTEWATER PLAN. ADDITIONAL FIRE HYDRANTS
 WILL BE REQUIRED.
  
 4. THE PROPOSED FIRE DEPARTMENT CONNECTION SHALL BE
 EQUIPPED WITH LOCKING KNOX CAPS.
  
 5. ELECTRONIC TAMPER SWITCHES, CHAIN AND LOCK REQUIRED
 ON FIRELINE BACKFLOW DEVICE.
  
 6. DEMOLITION PERMIT REQUIRED FOR THE REMOVAL OF THE
 EXISTING ONE STORY BUILDINGS.
  
 7. SUBMIT COMPLETE ARCHITECTURAL, MECHANICAL,
 ELECTRICAL, PLUMBING, FIRE SPRINKLER AND FIRE ALARM
 DRAWINGS.
  
 8. A KNOX-BOX WILL BE REQUIRED.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 10. THE FIRE SPRINKLER AND FIRE ALARM SYSTEM SHALL BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 11. PLEASE PROVIDE A LIFE SAFETY PLAN ILLUSTRATING ALL
 LIFE SAFETY FEATURES. THESE INCLUDE EXIT DOORS, EXIT
 SIGNS, EMERGENCY LIGHTS, TACTILE SIGNAGE, FIRE ALARM,
 AND PORTABLE FIRE EXTINGUISHING EQUIPMENT.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX