Date Text
2009-11-30 16:58:35PLEASE PROVIDE MORE SPECIFIC INFORMATION AS TO THE TYPE
 OF INSTITUTION PROPOSED TO DETERMINE WATER USAGE
 DEMANDS. IT IS UNDERSTOOD THAT THE PROPOSED ADDITION IS
 TO BE A "CULTURAL FACILITY", BUT MORE SPECIFICALLY,
 WHAT OTHER WATER USAGES SHALL BE REQUIRED. THIS DATA
 WILL DETERMINE THE SERVICE SYSTEM TYPE AND SIZE
 ADEQUATE TO SERVICE THE FACILITY.
  
 THE LOCATION OF THE PROPOSED WATER SERVICES CROSS
 CONNECTIONS, I.E., DDCV AND RPZ AND WATER METER, MAY
 HAVE TO BE REPOSITIONED/MOVED CLOSER TO THE WATER MAIN
 CONNECTION.
  
 CURRENTLY SOLID WASTE REMOVAL AT THIS SITE IS A 4
 CU./YDS. DUMPSTER WITH NO ENCLOSURE.
 PLEASE PROVIDE AN EASILY ACCESSIBLE SPACE FOR A
 DUMPSTER ENCLOSURE PER CITY'S STANDARD DETAIL GC-9.
  