Plan Review Notes
Plan Review Notes For Project Z09090011
Project Number Z09090011
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-09-24 09:56:46INFORMAL SITE PLAN REVIEW NO. 09-04 (Z09090011)
 10,400 SQUARE FOOT MEDICAL OFFICE BUILDING
  
 1. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED. THESE
 NUMBERS SHALL CONTRAST TO THE BACKGROUND THEY ARE
 AFFIXED TO. SHOWN ON PAGE A-2 P2.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM INSTALLATION.
  
 4. A FIRE HYDRANT IS REQUIRED TO BE WITHIN 150 FEET OF
 THE FIRE DEPARTMENT CONNECTION.
  
 5. THE FIRE DEPARTMENT CONNECTION IS TO BE EQUIPPED
 WITH KNOX LOCKING CAPS.
  
 6. THE FIRE ALARM AND FIRE SPRINKLER SYSTEM IS TO BE
 SUPERVISED BY A UL LISTED CENTRALS STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 7. FIRE HYDRANTS SHALL MEET UTILITY AND FIRE RESCUE
 STANDARDS.
  
 8. A KNOX-BOX IS REQUIRED FOR THE PROPERTY.
  
 9. A SITE PLAN DISPLAYS ONLY ONE FIRE HYDRANT.
 ADDITIONAL FIRE HYDRANTS WILL BE NEEDED TO PROTECT
 20,800 SQUARE FEET.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 804-4709 PHONE
 804-4774 FAX
 [email protected]
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved