| Plan Review Notes For Project Z09090011 |
| Project Number |
Z09090011 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-24 09:56:46 | INFORMAL SITE PLAN REVIEW NO. 09-04 (Z09090011) | | | 10,400 SQUARE FOOT MEDICAL OFFICE BUILDING | | | | | | 1. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6" | | | HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED. THESE | | | NUMBERS SHALL CONTRAST TO THE BACKGROUND THEY ARE | | | AFFIXED TO. SHOWN ON PAGE A-2 P2. | | | | | | 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE | | | SPRINKLER SYSTEM INSTALLATION. | | | | | | 4. A FIRE HYDRANT IS REQUIRED TO BE WITHIN 150 FEET OF | | | THE FIRE DEPARTMENT CONNECTION. | | | | | | 5. THE FIRE DEPARTMENT CONNECTION IS TO BE EQUIPPED | | | WITH KNOX LOCKING CAPS. | | | | | | 6. THE FIRE ALARM AND FIRE SPRINKLER SYSTEM IS TO BE | | | SUPERVISED BY A UL LISTED CENTRALS STATION APPROVED FOR | | | CENTRAL STATION SERVICE. | | | | | | 7. FIRE HYDRANTS SHALL MEET UTILITY AND FIRE RESCUE | | | STANDARDS. | | | | | | 8. A KNOX-BOX IS REQUIRED FOR THE PROPERTY. | | | | | | 9. A SITE PLAN DISPLAYS ONLY ONE FIRE HYDRANT. | | | ADDITIONAL FIRE HYDRANTS WILL BE NEEDED TO PROTECT | | | 20,800 SQUARE FEET. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | WEST PALM BEACH FIRE RESCUE | | | BUREAU OF FIRE PREVENTION | | | 500 NORTH DIXIE HIGHWAY | | | WEST PALM BEACH, FLORIDA 33401 | | | 804-4709 PHONE | | | 804-4774 FAX | | | [email protected] |
| |
Print |
|