| Plan Review Notes For Project Z09080026 |
| Project Number |
Z09080026 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-27 12:52:28 | PLANNING BOARD CASE NUMBER 970O | | | | | | 1. THE MEZZANINE FLOOR AREA APPEARS TO BE INCORRECT. | | | THE TOTAL FLOOR AREA MAY ALSO BE INCORRECT DUE TO THE | | | MEZZANINE TOTAL. | | | | | | 2. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | | FOR HANDRAILS AND GUARDRAILS. | | | | | | 3. DUST WALLS SHALL NOT BE CONSTRUCTED OF NON-FIRE | | | RATED VISQUEEN. | | | | | | 4. CARE SHOULD BE TAKEN TO AVOID THE BUILD-UP OF CARBON | | | MONOXIDE (CO) DURING THE USE OF GASOLINE POWERED SAWS. | | | CARBON MONOXIDE IS A COLORLESS, ODORLESS, AND FLAMMABLE | | | IN THE RIGHT CONCENTRATION. PROPER VENTILATION CONTROLS | | | SHALL BE USED TO PREVENT ILLNESS OR INJURY. | | | | | | 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 6. ANY REQUIRED FIRE PROTECTION SYSTEM THAT IS OUT OF | | | SERVICE FOR MORE THAN FOUR HOURS IN A TWENTY FOUR | | | PERIOD WHICH WILL REQUIRE A FIRE WATCH. ALL FIRE WATCH | | | ACTIVITIES SHALL BE REQUESTED IN WRITING TO THE BUREAU | | | OF FIRE PREVENTION | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
| |