Plan Review Notes
Plan Review Notes For Project Z09080026
Project Number Z09080026
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-08-27 12:52:28PLANNING BOARD CASE NUMBER 970O
  
 1. THE MEZZANINE FLOOR AREA APPEARS TO BE INCORRECT.
 THE TOTAL FLOOR AREA MAY ALSO BE INCORRECT DUE TO THE
 MEZZANINE TOTAL.
  
 2. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
 3. DUST WALLS SHALL NOT BE CONSTRUCTED OF NON-FIRE
 RATED VISQUEEN.
  
 4. CARE SHOULD BE TAKEN TO AVOID THE BUILD-UP OF CARBON
 MONOXIDE (CO) DURING THE USE OF GASOLINE POWERED SAWS.
 CARBON MONOXIDE IS A COLORLESS, ODORLESS, AND FLAMMABLE
 IN THE RIGHT CONCENTRATION. PROPER VENTILATION CONTROLS
 SHALL BE USED TO PREVENT ILLNESS OR INJURY.
  
 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 6. ANY REQUIRED FIRE PROTECTION SYSTEM THAT IS OUT OF
 SERVICE FOR MORE THAN FOUR HOURS IN A TWENTY FOUR
 PERIOD WHICH WILL REQUIRE A FIRE WATCH. ALL FIRE WATCH
 ACTIVITIES SHALL BE REQUESTED IN WRITING TO THE BUREAU
 OF FIRE PREVENTION
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX