2009-09-04 16:57:331. SIGNAGE WILL BE REVIEWED AT THE TIME OF PERMIT,
 HOWEVER, PLEASE KNOW THAT THE MAXIMUM PERMISSIBLE SIGN
 HEIGHT IN THE NEIGHBORHOOD COMMERCIAL ZONING DISTRICT
 IS 10 FEET. SEE SECTION 94-408(A) FOR THE FULL LISTING
 OF REQUIREMENTS.
 2. THE LOADING ZONE IS UNDERSIZED. THE MINIMUM SIZE IS
 10 FEET BY 25 FEET. SEE SECTION 94-485, TABLE XV-4.
 3. PLEASE CLARIFY WHAT IS MEANT BY THE NOTE BILL BOARD
 ON THE ELEVATIONS. IS THERE ANY EXISTING SIGNAGE
 PROPOSED TO BE INSTALLED THERE? IF SO, PLEASE PROVIDE
 DETAILS AND NOTE THAT IT MUST COMPLY WITH SECTION
 94-408(A) AS REFERENCED ABOVE.
 4. THE LANDSCAPE PLAN DOES NOT SHOW THE GENERATOR WHICH
 APPEARS ON THE SITE PLAN. PLEASE REVISE THE LANDSCAPE
 PLAN ACCORDINGLY AND PROVIDE THE REQUIRED SCREENING.
 5. PLEASE PROVIDE DETAILS OF THE GENERATOR ENCLOSURE.
 IS THIS AN UNROOFED OR ROOFED STRUCTURE? THE PLANS
 AREN???T CLEAR ON THIS.
 6. PLEASE PROVIDE DETAILS ON THE BICYCLE PARKING,
 INCLUDING THE BRAND AND MODEL OF RACK TO BE USED.
 PLEASE CONTACT ALEX HANSEN, SENIOR PLANNER, AT
 561-822-1463 FOR THE SPECIFICS ON WHAT TYPES OF BICYCLE
 RACKS WILL WORK BEST FOR YOUR APPLICATION. PLEASE NOTE
 THAT HE WILL BE OUT OF THE OFFICE UNTIL SEPT. 11TH.
 7. PLEASE INCLUDE THE CORRECT CITY-DETAIL FOR THE
 PARKING LOT STRIPING. THIS CAN BE PROVIDED TO YOU AFTER
 THE PPRC MEETING IF YOU DO NOT ALREADY HAVE IT.
 8. THE SURVEY SHOWS TWO 6 FOOT WIDE UTILITY EASEMENTS
 RUNNING EAST AND WEST THROUGH THE MIDDLE OF THE
 PROPERTY. PLEASE CONFIRM THAT THESE EASEMENTS STILL
 EXIST, IF SO, THEY WILL NEED TO BE ABANDONED.
 9. THE IMPERMEABLE SQUARE FOOTAGE SHOULD INCLUDE PAVING
 AND BUILDING AREA. WHEN ADDED TO THE PERMEABLE (IE
 LANDSCAPED) AREA, THAT FIGURE SHOULD EQUAL THE TOTAL
 SQUARE FOOTAGE OF THE LOT.
 10. THERE IS AN EXISTING CATCH BASIN WITHIN THE RIGHT
 OF WAY ON PALM BEACH LAKES BLVD. PLEASE ADD THIS BASIN
 TO THE SITE PLAN. IT APPEARS THAT IT MAY INTERFERE WITH
 THE LOCATION OF THE DRIVEWAY.
 11. PLEASE CLARIFY WHAT IS AND IS NOT CURBED ON THE
 SITE PLAN. IT APPEARS THAT THERE IS A CURB BETWEEN THE
 HANDICAP SPACE AND THE DRIVE AISLE. ALSO, IT APPEARS
 THAT SIDEWALK USERS WILL HAVE TO CROSS OVER A CURB WHEN
 TRAVERSING THE DRIVE AISLES ON BOTH SIDES OF THE
 PROPERTY. THESE ARE BOTH CONDITIONS WHICH MAY NOT
 EXIST. PLEASE CLEARLY SHOW ON THE PLAN WHERE CURBING IS
 PROPOSED TO BE INSTALLED.
 12. PLEASE PROVIDE AN ACCESSIBLE ROUTE FROM THE
 SIDEWALK TO THE BUILDING ENTRY.
 13. PLEASE INCLUDE A NOTE ON THE PLANS THAT ALL CURBING
 SHALL BE FDOT D TYPE CURB.
  