| 2009-08-03 15:21:15 | NOTE: ENGINEERING SERVICES HAS NO OBJECTION TO AMEND |
| | THE SITE TO INCLUDE A PROPOSED ORTHODONTIST'S OFFICE. |
| | HOWEVER PLEASE OBSERVE THE FOLLOWING CONCERNS THIS |
| | DEPARTMENT REQUESTS: |
| | |
| | |
| | 1. PRELIMINARY ENGINEERING/WATER SERVICE |
| | PLANS/CONNECTIONS ARE NOT SHOWN AS PER CITY OF WEST |
| | PALM BEACH'S STANDARDS (WS-9 & WS-10). THE DISTANCES |
| | SHOWN (SHEET C-1) BETWEEN THE DCDA, BFP AND PROPERTY |
| | LINE, EXCEED THE ALLOWABLE DISTANCE (3 FEET MAXIMUM). |
| | IT WILL BE NECESSARY TO REDESIGN THE CONFIGURATION OF |
| | THE LOCATION OF THESE CROSS-CONNECTIONS TO A SMALLER |
| | FOOTPRINT/EASEMENT AND MORE CONFINED TO THE S.E. CORNER |
| | OF THE PROPERTY. |
| | |
| | 2. SHEET C-1 SHOWS A TRUCK INSIDE THE LOWER PARKING |
| | LEVEL. THIS IS INSUFFICIENT CLEARANCE (26 FEET MIN. |
| | UNOBSTRUCTED VERTICAL HEIGHT), TO OPERATE A SANITATION |
| | TRUCK, IF THAT IS THE INTENT. IT WAS ALSO PREVIOUSLY |
| | AGREED UPON TO SERVICE SOLID WASTE DUMPSTERS AT A |
| | STAGING AREA ON THE SERVICE ENTRANCE DRIVEWAY. |
| | |
| | 3. PLEASE PROVIDE TECHNICAL PLAN DETAILS DEPICTING THE |
| | STRUCTURAL INTEGRITY OF THE PROPOSED BARRIER WALL/FLOOR |
| | SYSTEM FOR THE PROPOSED MULTI-LEVEL UNDERGROUND PARKING |
| | FACILITIES THAT IS SUFFICIENT TO ENSURE THE ENTIRE |
| | UNDERGROUND COMPLEX SHALL REMAIN PROTECTED FROM WATER |
| | INTRUSION AT THE PROPOSED FLOOD ZONE A5 SITE, (AT |
| | PLUS/MINUS ELEVEN FEET BELOW SEA LEVEL), SHALL KEEP THE |
| | FACILITY DRY AT ALL TIMES. |
| | |
| | PLEASE CONTACT THE REVIEWER FOR ANY QUESTIONS: |
| | |