| 2009-07-29 15:40:53 | ZONING BOARD OF APPEALS CASE NUMBER 3254 |
| | |
| | 1. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6" |
| | HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED. |
| | |
| | 2. ILLUMINATED EXIT SIGNS, EMERGENCY LIGHTING |
| | APPLIANCES, AND PORTABLE FIRE EXTINGUISHERS ARE |
| | REQUIRED. PLEASE DISPLAY ALL FIRE SAFETY EQUIPMENT. |
| | |
| | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | INSTALLATION OF THE UNDERGROUND FUEL TANKS. |
| | |
| | 4. PLANS WHEN SUBMITTED SHALL INDICATE THE LOCATION OF |
| | EMERGENCY STOP EQUIPMENT. ALL WARNING SIGNS, AND FIRE |
| | EXTINGUISHING EQUIPMENT FOR THE FUEL AREA SHALL BE |
| | SHOWN. |
| | |
| | 5. THE INSTALLATION, USE AND OPERATION OF THIS FUEL |
| | STATION SHALL COMPLY WITH NFPA 30A, MOTOR FUEL |
| | DISPENSING FACILITIES AND REPAIR GARAGES. |
| | |
| | 6. THE DISPENSING OF FUELS INTO NON-APPROVED CONTAINERS |
| | IS PROHIBITED. |
| | |
| | 7. THE PROPOSED FIRE HYDRANT SHALL MEET UTILITY AND |
| | FIRE RESCUE STANDARDS. |
| | |
| | 8. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION IS TO |
| | COMPLY WITH NFPA 241. |
| | |
| | 9. ALL FUEL DISPENSING EQUIPMENT TO INCLUDE THE HOSES |
| | SHALL COMPLY WITH NFPA 30A. |
| | |
| | 10. APPROVED AND LISTED BREAKAWAY DEVICES WILL BE |
| | REQUIRED FOR THE FUEL APPURTENANT EQUIPMENT. |
| | |
| | 11. EMERGENCY PROCEDURES ARE TO BE DEVELOPED FOR THE |
| | FUEL STATION. |
| | |
| | 12. THIS LIST SHALL NOT BE CONSIDERED ALL INCLUSIVE FOR |
| | CODE REQUIREMENTS. |
| | |
| | |