2009-07-29 15:40:53ZONING BOARD OF APPEALS CASE NUMBER 3254
  
 1. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED.
  
 2. ILLUMINATED EXIT SIGNS, EMERGENCY LIGHTING
 APPLIANCES, AND PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED. PLEASE DISPLAY ALL FIRE SAFETY EQUIPMENT.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE UNDERGROUND FUEL TANKS.
  
 4. PLANS WHEN SUBMITTED SHALL INDICATE THE LOCATION OF
 EMERGENCY STOP EQUIPMENT. ALL WARNING SIGNS, AND FIRE
 EXTINGUISHING EQUIPMENT FOR THE FUEL AREA SHALL BE
 SHOWN.
  
 5. THE INSTALLATION, USE AND OPERATION OF THIS FUEL
 STATION SHALL COMPLY WITH NFPA 30A, MOTOR FUEL
 DISPENSING FACILITIES AND REPAIR GARAGES.
  
 6. THE DISPENSING OF FUELS INTO NON-APPROVED CONTAINERS
 IS PROHIBITED.
  
 7. THE PROPOSED FIRE HYDRANT SHALL MEET UTILITY AND
 FIRE RESCUE STANDARDS.
  
 8. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION IS TO
 COMPLY WITH NFPA 241.
  
 9. ALL FUEL DISPENSING EQUIPMENT TO INCLUDE THE HOSES
 SHALL COMPLY WITH NFPA 30A.
  
 10. APPROVED AND LISTED BREAKAWAY DEVICES WILL BE
 REQUIRED FOR THE FUEL APPURTENANT EQUIPMENT.
  
 11. EMERGENCY PROCEDURES ARE TO BE DEVELOPED FOR THE
 FUEL STATION.
  
 12. THIS LIST SHALL NOT BE CONSIDERED ALL INCLUSIVE FOR
 CODE REQUIREMENTS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX