Plan Review Notes
Plan Review Notes For Project E23020006
Project Number E23020006
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2023-03-13 14:15:06E23020006 ??? HOWARD PARK TENNIS CENTER ??? INITIAL
 REVIEW 2.8.2023
  
 COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
  
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER.
 3. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 4. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND
 IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS,
 AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. GATE
 VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR SIDEWALK.
 ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE
 VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON
 PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. PLEASE
 SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPES SIZES AND
 MATERIALS, LOCATED ON THE RIGHT-OF-WAY.
 5. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION, AND
 EXISTING METER AND BACKFLOW (TO BE REMOVED?). BACKFLOWS
 SHALL BE INSTALLED ON PRIVATE PROPERTY OUTSIDE OF
 EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER METERS
 SHALL BE INSTALLED IMMEDIATELY ADJACENT TO PROPERTY
 LINE. 3 INCH AND LARGER WATER METERS SHALL BE INSTALLED
 ABOVE-GROUND ONLY.
 6. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA
 AND FIRE BACKFLOW PREVENTER AS DCDA. SPECIFY LEAD FREE
 DESIGN ON ALL BACKFLOWS.
 7. SHEET C.100 ??? DEMO PLAN HAS LEGEND SYMBOL FOR SILT
 FENCE, BUT SILT FENCE IS NOT CALLED OUT ON DRAWING.
 8. SHEET H.200 ??? BACKFLOWS CALLED OUT ON THIS SHEET
 ARE NOT SHOWN ON UTILITY SHEET.
 9. SHEET C5.10 ??? STANDARD DETAILS ARE ILLEGIBLE.
 10. PLEASE SHOW ALL EXISTING AND PROPOSED UNDERGROUND
 UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS,
 AND CABLEVISION & TELECOMMUNICATION FACILITIES WITH
 PIPE MATERIAL AND SIZE.
 11. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 12. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 13. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
 -SURVEY REPORT NOTE 6 SAYS THAT THERE MAY BE ADDITIONAL
 EASEMENTS AND RESTRICTIONS, BUT NO SEARCH OF PUBLIC
 RECORD WAS MADE. SHOULD CONDUCT PUBLIC RECORD SEARCH.
 -SURVEY IS NOT SIGNED, SEALED, AND DATED.
 -WPB GIS SAYS THERE IS A LIFT STATION AND FORCE MAIN IN
 THE AREA SHOWN ON DEMO PLAN. PLEASE SHOW AND LABEL WITH
 WHAT IS HAPPENING TO IT.
 -SHEET C5.00: UTILITY BILLING SYSTEM INDICATES THAT
 EXISTING WATER METER IS 1.5 INCH INSTEAD OF 2 INCH.
 -UTILITY PLAN IS NOT CLEAR ON WHAT THE WATER AND
 PLUMBING IS BEING USED FOR OTHER THAN THE DRINKING
 FOUNTAIN. IF PLUMBING HAS OTHER USES SUCH AS
 IRRIGATION, IS ANY OTHER ISOLATION PLUMBING BACKFLOW
 PROTECTION NEEDED?
 -WILL THE EXISTING METER FEED THE EXISTING BUILDING?
 -ON UTILITY PLAN, SHOW EXISTING WATER MAIN AND FORCE
 MAIN AS SHOWN ON SHEET C4.00. SHOW OTHER UTILITIES
 INCLUDING ANY FRANCHISE UTILITIES, STORMWATER
 UTILITIES, SEWER LATERALS, CLEANOUTS, AND LIFT
 STATIONS.
 -UTILITY PLAN DOES NOT HAVE WATER DEMAND CALCULATIONS.
 -SHOW EXISTING WATER METER BOX AND BACKFLOW ASSEMBLY ON
 ALL PLAN SHEETS.
 -SHEET H2.00 SHOWS TWO NEW WATER METERS AND TWO NEW
 BACKFLOW ASSEMBLIES. IF THOSE ARE COMING OFF OF CITY
 WATER MAIN AND NOT SUB-METERS, THEN SHOW AND LABEL ON
 UTILITY PLAN. ALSO ADD ASSOCIATED WATER SERVICE
 STANDARD DETAILS TO PLAN SET.
 -SHEET H2.00: ON LABEL FOR PROPOSED BACKFLOW ASSEMBLIES
 SPECIFY RP TYPE BACKFLOW ASSEMBLY. ALSO ADD NOTE TO USE
 WILKINS ZURN 975XL2 BACKFLOW ASSEMBLY.
 -BACKFLOW CAGES AND CONCRETE PADS MAY BE REQUIRED. CAN
 CONTACT GREG MIHALKO [email protected] FOR
 DETERMINATION.
 -SHOW UTILITIES ON LANDSCAPING PLAN SHEET L1.00.
 -FOR THE 10 HP PUMP STATION SHOWN ON L2.00, DOES THE
 IRRIGATION WATER COME FROM A WELL OR THE POND?
 -WILL THERE BE ANY BATHROOMS AT THE TENNIS COURT AREA?
 IF SO, SHOW AND LABEL THE WASTEWATER SYSTEM.
 -WILL THERE BE ANY FOOD SERVICE AT THE TENNIS COURT
 AREA? IF SO, SHOW AND LABEL ANY EXTERIOR GREASE TRAPS.
 -WILL THE BUILDING HAVE ANY FIRE SPRINKLERS?
  
 COMMENTS FROM RICKY ELIZONDO, E.I., UTILITIES PLANS
 EXAMINER, PUBLIC UTILITIES [email protected]
 561-764-8010 (CELL)
 -SHOW ALL EXISTING UTILITIES AND THEIR APPURTENANCES
 THAT ARE WITHIN THE SCOPE OF THE PROJECT (WATER,
 WASTEWATER, STORM, AND DRY UTILITIES)
 -PROPOSED IRRIGATION METER INSTALLATION NEEDS TO BE
 REFLECTED ON THE PLANS
 -PROVIDE A DEMAND TABLE EXHIBITING EXISTING CONDITIONS
 AND PROPOSED CONDITIONS
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 DRAINAGE CALCS
 1. WATER QUALITY TREATMENT SHOULD BE PROVIDED FOR NEW
 IMPERVIOUS SURFACES, NOT THE NET INCREASE IN IMPERVIOUS
 SURFACE UNLESS TREATMENT IS ALREADY BEING PROVIDED.
 2. USE THE SAME VERTICAL DATUM IN THE CALCULATIONS THAT
 IS USED ON THE ENGINEERING PLANS.
 3. HOW WAS THE WATER TABLE ELEVATION OF 2.00 FT NGVD
 DETERMINED. THE ADJACENT STUB CANAL IS MAINTAINED AT
 ELEVATION 8.0 FT NGVD.
 4. NO DESIGN INFORMATION IS PROVIDED FOR THE
 EXFILTRATION TRENCH OTHER THAN 24??? DIAMETER PIPE, THE
 TRENCH HEIGHT OF 4 FEET (PER THE DETAIL ON SHEET
 C-5.00) AND TOTAL EXFILTRATION TRENCH LENGTH OF 60
 FEET. THE TRENCH WIDTH SCALES 5??? ON SHEET C-4.00. THE
 LOWEST RIM ELEVATION IS 13.50 FT NAVD. THE CALCULATIONS
 DIMENSIONS INDICATE TRENCH DEPTH OF 13.5 FEET, TRENCH
 WIDTH OF 5 FEET.
 5. HOW IS THE FACTOR OF SAFETY INCLUDED IN THE LAST
 LINE OF SECTION 3 ON PAGE 2?
 6. REVISE DRAINAGE CALCULATIONS PER THE DESIGN PLANS.
  
 PLANS
 1. ON EVERY SHEET WITH ELEVATION INFORMATION, LIST THE
 VERTICAL DATUM USED AND THE CONVERSION EQUATION BETWEEN
 THE VERTICAL DATUM USED AND NGVD1929.
 2. SHOW AND LABEL THE EXISTING FORCEMAIN FROM THE LIFT
 STATION.
 3. SHOW UTILITIES ON THE LANDSCAPE PLANS.
 4. PROVIDE THE TOP AND BOTTOM ELEVATIONS FOR THE
 EXFILTRATION TRENCH AND THE TRENCH WIDTH ON THE
 EXFILTRATION TRENCH DETAIL.
 5. CONSIDER REGRADING THE AREA BETWEEN THE SIDEWALKS
 AND TENNIS/PICKLEBALL COURTS FOR DRY STORMWATER
 RETENTION INSTEAD OF CONSTRUCTING EXFILTRATION TRENCHES
 (WHICH ONLY A FRACTION OF THE STORMWATER RUNOFF FROM
 THE COURTS SURFACE WILL BE COLLECTED AND TREATED.
 6. THE LOCATION OF THE EXFILTRATION TRENCHES MAY IMPACT
 THE ROOT SYSTEMS (AND VICE VERSA) OF THE EXISTING
 TREES.
 7. REVIEW THE STORMWATER DRAINAGE CONSTRUCTION NOTES ON
 SHEET C-5.00 AND MODIFY/DELETE PER THE SITE AND DESIGN
 CONDITIONS.
 8. USE A DARKER COLOR FOR THE WATER/SEWER NOTES ON
 SHEET C5.00.
  
  