2023-06-22 10:27:24E23010043 - 512 CLEMATIS ST RESUB 4.21.23
  
 NO COMMENTS FROM LINDA QUINONES, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1085
 [email protected] :
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
 -ADD WATER SERVICE STANDARD DETAILS WS1 AND WS6 TO PLAN
 SET. RECOMMEND ADDING THEM TO IRRIGATION PLAN SET ALSO.
  
 -LANDSCAPING PLAN PLANT LOCATIONS CONFLICT WITH
 UTILITIES AND DOES NOT SHOW PROPOSED UTILITY LOCATIONS
 THAT MATCH CIVIL ENGINEERING PLAN. PLEASE INCLUDE
 UPDATED/REVISED LANDSCAPING PLAN IN RESUBMITTAL
 PACKAGE.
  
 -PROVIDE FOLLOW-UP AS REFERENCED IN LAST RESPONSE
 LETTER: [COMMUNICATE WITH GREG MIHALKO [email protected]
 FROM WPB PARKS DEPARTMENT CONCERNING THE PPRC
 IRRIGATION CONDITIONS AS THE EXISTING METER AND
 BACKFLOW PROPOSED TO BE RELOCATED IS FOR PARKS
 IRRIGATION. VERIFY HIS APPROVAL AND INDICATE WHAT HIS
 DIRECTIONS ARE. ALSO INDICATE IF ANOTHER METERED WATER
 SERVICE IS NEEDED, OR IF PRIVATE IRRIGATION WILL RUN
 OFF 3 INCH DOMESTIC METER.] - I EMAILED GREG MIHALKO ON
 APRIL 3 AND 4, 2023 AND WILL CONFIRM HIS APPROVAL OR
 DIRECTION ONCE I RECEIVE IT.
  
 -PLANS NEED TO BE SIGNED, SEALED, AND DATED BY LICENSED
 ENGINEER.
  
 -CALLOUT PIPE MATERIAL TYPE AND SIZE OF FIRE LINE WATER
 SERVICE AND WATER SERVICE FOR 3 INCH METER.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
  
 1. PROVIDE VERTICAL DATUM REFERENCE AND CONVERSION
 EQUATION TO NGVD1929 ON SHEETS 4 AND 5.
 2. PROVIDE FINAL DESIGN PLAN(S) FOR THE RTANKS. NOTE
 ONLY ONE SHEET, DATED 1/3/2023, WAS INCLUDED IN THE
 APRIL 2023 SUBMTITAL.
 3. REGARDING THE TYPICAL CROSS SECTIONS, PARTICULARLY
 AT DOORWAYS, REVIEW THE FLORIDA BUILDING CODE FOR THE
 MINIMUM REQUIRED LENGTH AND MAXIMUM ALLOWABLE SLOPE FOR
 LANDINGS OUTSIDE OF DOORS. THIS INFORMATION MAY BE
 FOUND IN CHAPTER 1010.1.5 AND 1010.1.6. REVISE THE
 AFFECTED SECTIONS AND VERIFY THE SIDEWALKS AT DOORWAYS
 WILL MEET THE EXISTING BACK OF SIDEWALK ELEVATION.
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
  
 PRIOR COMMENTS NOT ADDRESSED FROM APRIL 20, 2023
 -COMMENT 1: CITY???S RECORD SHOWS THERE ARE (2) WATER
 SERVICES SERVING 512 CLEMATIS STREET FROM CLEMATIS
 STREET. THESE SERVICES NEED TO BE CUT AND CAP AT THE
 MAIN ON CLEMATIS STREET. EXISTING WATER AND SEWER
 SERVICES CURRENTLY SERVING THE PROPERTY, IF NOT USED,
 NEEDS TO BE CUT AND CAP AT THE MAIN.
 -COMMENT 3: PROVIDE A PROFILE FOR THE PROPOSED SANITARY
 SEWER LATERAL FROM THE PROPOSED MANHOLE/POINT OF
 CONNECTION TO THE PROPOSED CLEAN-OUT/POINT OF SERVICE.
 CALL OUT ALL UTILITY CROSSINGS WITH HORIZONTAL AND
 VERTICAL CLEARANCES.
 -COMMENT 5: REFER TO APPLICABLE CITY STANDARD DETAILS
 FOR PROPOSED SEWER LATERAL CONNECTION AND PLACEMENT OF
 CLEANOUT (GS 1-8)
 -COMMENT 6: THE CONNECTION FROM THE GREASE TRAP NEED TO
 BE MADE NORTH OF THE PROPOSED CLEANOUT/POINT OF
 SERVICE. EOR TO CONFIRM WHETHER A SEPARATE CONNECTION
 IS REQUIRED FOR FLOWS FROM GREASE TRAP.
  
 PRIOR COMMENTS NOT ADDRESSED FROM FEBRUARY 2022 PPRC
 SUBMITTAL
 -COMMENT 2: REPLACE EXISTING SANITARY SEWER LINE
 FRONTING THE PROPERTY UP TO SANITARY MANHOLE ON
 QUADRILLE PLAZA DRIVE. THE LIMITS OF THE CITY???S
 CLEMATIS STREET SOUTH ALLEYWAY IMPROVEMENTS WILL START
 FROM THE SW CORNER OF 512 CLEMATIS PROPERTY HEADING
 WEST TO ROSEMARY.
 -COMMENT 3: PERFORM SOFTDIGS AS REQUIRED TO CALL OUT
 HORIZONTAL AND VERTICAL CLEARANCES, AS WELL AS TO
 CONFIRM EXISTENCE OF DRY UTILITIES AND
  
 NEW COMMENTS:
 1. PLAN SHEETS NEED TO BE SET UP TO PRINT TO SCALE ON
 11???X17???
 2. THIS PROJECT FALLS WITHIN LS 40 SERVICE BOUNDARY.
 MODIFY ON PLANS FROM LS 43 TO LS 40.
 3. CITY???S RECORD SHOWS THAT THE EXISTING WATER LINE
 IN THE ALLEYWAY IS NOT LOOPED AND IS POSSIBLY
 UNDERSIZED WEST OF QUADRILLE PLAZA DRIVE. THE EXISTING
 WATER MAIN FRONTING THE PROPERTY NEEDS TO BE REPLACED.
  
  
  