Plan Review Notes
Plan Review Notes For Project E23010043
Project Number E23010043
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2023-03-02 15:45:33E23010043 - 512 CLEMATIS ST 1.31.23 SUBMITTAL
  
 COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 3. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER.
 4. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 5. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 6. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND
 IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS,
 AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. GATE
 VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR SIDEWALK.
 ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE
 VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON
 PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. PLEASE
 SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPES SIZES AND
 MATERIALS, LOCATED ON THE RIGHT-OF-WAY.
 7. PLEASE CUT AND CAP UTILITIES NOT IN USE AND REMOVE
 ANY ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM
 CITY RIGHT OF WAY.
 8. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS,
 INCLUDING THOSE PROPOSED TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITY WATER METERS.
 9. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION, AND
 EXISTING METER AND BACKFLOW (TO BE REMOVED?). BACKFLOWS
 SHALL BE INSTALLED ON PRIVATE PROPERTY OUTSIDE OF
 EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER METERS
 SHALL BE INSTALLED IMMEDIATELY ADJACENT TO PROPERTY
 LINE. 3 INCH AND LARGER WATER METERS SHALL BE INSTALLED
 ABOVE-GROUND ONLY.
 10. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA
 AND FIRE BACKFLOW PREVENTER AS DCDA. SPECIFY LEAD FREE
 DESIGN ON ALL BACKFLOWS.
 11. ENGINEERING PLANS SHALL INCLUDE PIGGING, FLUSHING
 AND SAMPLE POINTS ON ANY WATER RUNS 60 FT. IN LENGTH OR
 GREATER.
 12. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 13. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES AT ALL UTILITY CROSSINGS WITHIN ROW PER
 CITY OF WEST PALM BEACH STANDARD DETAIL GN-2 SERIES.
 PLEASE SHOW ALL EXISTING AND PROPOSED UNDERGROUND
 UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS,
 AND CABLEVISION & TELECOMMUNICATION FACILITIES WITH
 PIPE MATERIAL AND SIZE, LOCATED ON THE RIGHT-OF-WAY.
 14. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 15. PLEASE PROVIDE SANITARY ELEVATIONS AT MANHOLE
 TIE-IN.
 16. IF TRENCHING IN IN CITY-MAINTAINED ROADWAY AREAS
 ADD NOTE TO PROVIDE 50 FT. PAVEMENT RESTORATION
 TRANSITION ON EACH SIDE OF PROPOSED TRENCH PER CITY OF
 WPB STANDARD DETAIL GC-4.
 17. PLEASE COORDINATE WITH PUBLIC UTILITIES ABOUT
 ACCEPTANCE OF PROPOSED 4 FT. SANITARY MANHOLE. (5 FT.
 IS PREFERRED.)
 18. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 19. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -ADD WORDING ???ABOVE-GROUND??? TO LABEL OF PROPOSED 3
 INCH METER AS WELL AS REFERENCE TO WATER SERVICE
 STANDARD DETAIL WS3.
 -THERE SHOULD BE A 4 INCH GATE VALVE AND BYPASS BEFORE
 REDUCER FOR PROPOSED 3 INCH METER PER WS3.
 -SEPARATE THE CALLOUT FOR THE 3 INCH RPPA WITH ANOTHER
 LEADER LINE AND ADD REFERENCE TO WATER SERVICE STANDARD
 DETAIL WS7.
 -VERIFY DCDA LOCATION IS ACCEPTABLE WITH FIRE MARSHAL
 LEDUC.
 -PROVIDE SIGNED AND SEALED FIRE FLOW CALCULATIONS AS
 DIRECTED IN NOTE 9 WS5.
 -ON LABEL FOR DCDA ADD REFERENCE TO WATER SERVICE
 STANDARD DETAIL WS5.
 -ADD SHEETS TO PLAN SET WITH ASSOCIATED WPB STANDARD
 DETAILS. SHOULD SEE AT LEAST WS5, WS3, WS7, WS1, WS2,
 WS6 AND POSSIBLY OTHERS.
 -PROVIDE SIGNED AND SEALED FLOW CALCULATIONS AS
 DIRECTED IN NOTE 7 WS7.
 -METER AND BACKFLOW LOCATIONS SEEM TO HAVE CHANGED
 SINCE PPRC. ENSURE LANDSCAPING TREES AND BUSHES ARE
 DISTANCED FROM WATER METERS AND BACKFLOW ASSEMBLIES,
 AND PROVIDED UPDATED LANDSCAPING PLAN SHOWING THE
 REVISED METER AND BACKFLOW LOCATIONS.
 -ENSURE COMPLYING WITH CONDITIONS IN SITE PLAN APPROVAL
 LETTER ISSUED BY WPB PLANNING, INCLUDING THOSE
 REGARDING IRRIGATION.
 -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED
 CHEMICALS OR AUXILIARY WATER SYSTEM SUCH AS A WELL OR
 TANK.
 -COMMUNICATE WITH GREG MIHALKO [email protected] FROM
 WPB PARKS DEPARTMENT CONCERNING THE PPRC IRRIGATION
 CONDITIONS AS THE EXISTING METER AND BACKFLOW PROPOSED
 TO BE RELOCATED IS FOR PARKS IRRIGATION. VERIFY HIS
 APPROVAL AND INDICATE WHAT HIS DIRECTIONS ARE. ALSO
 INDICATE IF ANOTHER METERED WATER SERVICE IS NEEDED, OR
 IF PRIVATE IRRIGATION WILL RUN OFF 3 INCH DOMESTIC
 METER.
 -PLANS REFERENCE IRRIGATION PLANS. ADD COPY OF
 IRRIGATION PLANS IN RESUBMITTAL PACKAGE.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 1. ON EVERY SHEET WITH ELEVATION INFORMATION, LIST THE
 VERTICAL DATUM AND PROVIDE THE CONVERSION EQUATION TO
 NGVD1929.
 2. INDICATE WHERE PROPOSED EAST PROPERTY LINE IS
 DETERMINED BY DIMENSIONING THE NORTH AND SOUTH PROPERTY
 LINES AND/OR DIMENSION FROM THE RAILROAD RIGHT OF WAY
 LINE.
 3. PROVIDE CROSS SECTIONS FOR THE CLEMATIS ST AND
 QUADRILLE PLAZA DRIVE FRONTAGES FROM THE FACE OF THE
 BUILDING (PREFERABLY AT A DOOR OPENING) TO BEYOND THE
 CURB OR GUTTER. LABEL THE BUILDING LINE, R/W OR
 PROPERTY LINE, NAME OF THE R/W, SIDEWALKS,
 CURBS/GUTTERS, LANDSCAPING, PARKING, ETC. SHOW SURFACE
 BREAKS AND SURFACE SLOPES (AS PERCENTAGES). THE
 SIDEWALK IS NOT TO GO UP AND DOWN TO MEET THE DOOR
 OPENINGS ALONG THE BUILDING FRONTAGE. SHOW EXISTING
 CONDITIONS ON THE SECTIONS.
 4. HATCH ANY SIDEWALKS TO BE REPLACED WITHIN THE RIGHT
 OF WAY.
 5. LABEL THE SIZE AND MATERIAL OF ALL UTILITIES WITHIN
 THE RIGHT OF WAY.
 6. PROVIDE THE EXISTING INVERT AND RIM ELEVATIONS FOR
 THE EXISTING DRAINAGE STRUCTURE THAT IS BEING CONNECTED
 TO WITH THE ONSITE DRAINAGE SYSTEM.
 7. HOW WILL THE 1-FOOT SPACE BETWEEN THE BUILDINGS
 DRAIN?
 8. HOW WILL THE AREA CONNECTED TO THE WEST DRIVEWAY IN
 THE ALLEY DRAIN?
 9. COMPLETE THE DRAINAGE DESIGN. PROVIDE INVERT
 ELEVATIONS FOR THE 15??? RCP PIPE IN PLAN VIEW AND ON
 THE A3-C.S. DETAIL. R-TANK SYSTEM DETAILS HAVE NOTES
 STATING ??????SIZE TO BE DETERMINED DURING FINAL
 DESIGN??? AND ???10-INCH MAINTENANCE PORT (TYPICAL
 LOCATIONS TO BE VERIFIED BY ENGINEER)???.
 10. LABEL THE TOP AND BOTTOM ELEVATIONS OF THE R-TANK
 SYSTEM.
 11. DETAIL FOR A3-C.S. SHOWS ALL CONNECTING PIPES TO BE
 RCP. SITE DEVELOPMENT PLAN ONLY SHOWS THE OUTFALL PIPE
 AS RCP AND THE OTHER PIPES AS HDPE.
 12. REVISE THE TYPICAL PARKING SPACES DETAIL TO MATCH
 THE CITY???S LAYOUT IN SECTION 94-485 OF THE CITY???S
 CODE OF ORDINANCES. THERE IS 12 INCHES OF OPEN SPACE
 BETWEEN THE PARALLEL 4-INCH STRIPES AND THE ENDS OF THE
 PARALLEL STRIPES ARE CONNECTED WITH A 4-INCH STRIPE.
 13. INCLUDE THE CITY???S STANDARD DETAIL FOR TRENCH
 BACKFILL PAVEMENT RESTORATION.
 14. PROVIDE A DETAIL FOR INLET PROTECTION ON THE
 POLLUTION PREVENTION PLAN. THE PPP APPEARS TO SHOW
 USING STAKED SILT FENCE.
 15. NOTE ON THE LEFT SIDE OF THE PPP IS CUTOFF.
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
  
 -UNUSED SERVICE/METER ON NORTH END OF PROJECT WILL NEED
 TO BE REMOVED. (CUT AND CAP AT MAIN)
 -DIRECTION OF FLOW NOT SHOWN FOR PROPOSED SANITARY
 SEWER LATERAL
 -PROVIDE A PROFILE FOR SANITARY SEWER LATERAL FROM
 MANHOLE UP TO PROPERTY LINE. (THE APPROPRIATE CLEARANCE
 BETWEEN PROPOSED LATERAL AND EXISTING WM DOESN???T
 APPEAR TO BE MET).
 -CALL OUT PROPOSED MANHOLE AS ???DOGHOUSE??? MANHOLE
 -8??? CLEANOUT WILL BE REQUIRED FOR PROPOSED LATERAL
 (WILL SERVE AS CITY???S POINT OF SERVICE)
 -GREASE TRAP CONNECTION IS UNCLEAR, PLEASE SPECIFY
 (WILL CONNECTION BE MADE TO PROPOSED LATERAL OR
 EXISTING MAIN?)
 -6??? GATE VALVE FOR PROPOSED FIRE LINE WILL SERVE AS
 CITY???S POINT OF SERVICE, AN EASEMENT WOULD BE NEEDED
 IN THE PROPOSED LOCATION
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT (561) 494-1098 [email protected]
  
  