2023-06-09 15:53:00E23010020 - SUNVIEW MEDICAL CENTER - 1041 45TH ST.
 RESUB 4.24.23
  
 NO COMMENTS FROM LINDA QUI??ONES-CINTRON, PROJECT
 COORDINATOR, ENGINEERING SERVICES DEPT., 561-494-1085
 [email protected] :
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -PEAK WATER DEMAND WAS LISTED AT 143GPM. 2??? BADGER
 M170 METER WOULD BE USED FOR THIS APPLICATION, AND IT
 CANNOT BE USED IF FLOW WILL EXCEED 100GPM FOR 60
 MINUTES. PLEASE VERIFY FLOW WILL NOT EXCEED 100GPM FOR
 60 MINUTES AT ANY TIME.
  
 -POLY PIPE CANNOT BE USED BETWEEN METER AND BACKFLOW
 ASSEMBLY. CONSIDER REVISING LABEL FOR PIPING TO COMPLY
 WITH DETAIL WS1 AND WS6. (THOSE SHOW THE NECESSARY PIPE
 MATERIAL, REQUIRED DEPTH, AND REQUIRED SLEEVING)
  
 -DEMOLITION PLANS LABEL EXISTING WATER METER AS 2???,
 BUT IT IS CURRENTLY 3??? SIZE.
  
 NO COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 NO COMMENTS IN PREVIOUS SUBMITTAL
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
 -CITY RECORDS SHOW EXISTENCE OF SECOND WATER SERVICE
 CONNECTION FOR THIS PROPERTY. PLEASE VERIFY AND
 ELABORATE ON WHAT IS TO HAPPEN TO THIS SERVICE.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
  