| 2023-02-01 08:21:18 | E23010009 - 128 PALMETTO LN FIRST REVIEW |
| | |
| | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPT., 561-494-1098 |
| | [email protected] : |
| | 1. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND |
| | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM |
| | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE |
| | PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER. |
| | 2. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING |
| | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT |
| | HIM AT 561-494-2262 OR [email protected] |
| | 3. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND |
| | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND |
| | SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING |
| | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY |
| | SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND |
| | IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS, |
| | AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH |
| | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES |
| | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, |
| | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND |
| | MANHOLES AND PROFILES OF SANITARY SEWER LINES. GATE |
| | VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR SIDEWALK. |
| | ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE |
| | VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON |
| | PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. PLEASE |
| | SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT |
| | MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL |
| | EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT, |
| | INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES INCLUDING PIPES SIZES AND |
| | MATERIALS, LOCATED ON THE RIGHT-OF-WAY. |
| | 4. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED |
| | LOCATION OF WATER METER AND BACKFLOW PREVENTION, AND |
| | EXISTING METER AND BACKFLOW (TO BE REMOVED?). BACKFLOWS |
| | SHALL BE INSTALLED ON PRIVATE PROPERTY OUTSIDE OF |
| | EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER METERS |
| | SHALL BE INSTALLED IMMEDIATELY ADJACENT TO PROPERTY |
| | LINE. 3 INCH AND LARGER WATER METERS SHALL BE INSTALLED |
| | ABOVE-GROUND ONLY. |
| | 5. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA |
| | AND FIRE BACKFLOW PREVENTER AS DCDA. SPECIFY LEAD FREE |
| | DESIGN ON ALL BACKFLOWS. |
| | 6. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER |
| | AND STORM LINES AT ALL UTILITY CROSSINGS WITHIN ROW PER |
| | CITY OF WEST PALM BEACH STANDARD DETAIL GN-2 SERIES. |
| | PLEASE SHOW ALL EXISTING AND PROPOSED UNDERGROUND |
| | UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS, |
| | AND CABLEVISION & TELECOMMUNICATION FACILITIES WITH |
| | PIPE MATERIAL AND SIZE, LOCATED ON THE RIGHT-OF-WAY. |
| | 7. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE |
| | PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW |
| | DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING |
| | USC APPROVED LEAD-FREE DESIGN. |
| | 8. PLEASE CLEARLY LABEL ROAD RIGHT OF WAY. |
| | 9. PLEASE CLEARLY LABEL EXISTING LOCATION OF HYDRANT TO |
| | BE RELOCATED. |
| | 10. PLEASE PROVIDE/CONFIRM APPROVAL FROM FIRE |
| | DEPARTMENT FOR HYDRANT RELOCATION. |
| | 11. WHEN TRENCHING IN IN CITY-MAINTAINED ROADWAY AREAS |
| | ADD NOTE TO PROVIDE 50 FT. PAVEMENT RESTORATION |
| | TRANSITION ON EACH SIDE OF PROPOSED TRENCH PER CITY OF |
| | WPB STANDARD DETAIL GC-4. |
| | 12. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE |
| | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. |
| | 13. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND |
| | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER |
| | (E-XXXXXXXX). |
| | |
| | CONTACT INFO: |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR |
| | [email protected]: |
| | |
| | -RELOCATE BACKFLOW ASSEMBLIES OUT OF UTILITY EASEMENT. |
| | ENSURE THEY WILL NOT BE HIT BY ROLLING GATE. |
| | -PROVIDE SPOT ELEVATIONS AT METER BOX AND BACKFLOW |
| | ASSEMBLY LOCATIONS. |
| | -ADD RP TO BACKFLOW ASSEMBLY LABELS. |
| | -WILL THE HOUSE HAVE FIRE SPRINKLERS? IF SO, ADD A |
| | DEDICATED FIRELINE. |
| | -CALLOUT WATER SERVICE PIPE SIZE AND MATERIAL TYPE. |
| | -SHOW ANY EXISTING SEWER LATERAL CLEANOUTS. |
| | -SHOW EXISTING WATER SERVICES AND LABEL THEM FOR |
| | REMOVAL BACK TO THE WATER MAIN. |
| | -PROVIDE PROFILES OF FIRE HYDRANT RELOCATION AND WATER |
| | SERVICES. |
| | -SHOW AND LABEL ALL FRANCHISE UTILITIES NEAR WORK AREAS |
| | INCLUDING GAS, CABLE, ELECTRIC. |
| | -LABEL EXISTING FIRE HYDRANT PIPE WITH PIPE SIZE AND |
| | MATERIAL TYPE. |
| | -ADD MARKUP NOTE ON SD WS1 THAT DUAL CHECK IS NOT USED |
| | SINCE THERE IS A BACKFLOW ASSEMBLY. |
| | -FLOW TEST OF FIRE HYDRANT IS REQUIRED AFTER |
| | INSTALLATION. CONSIDER ADDING NOTE ON PLAN. |
| | -VERIFY NO TREES OR BUSHES WILL BE NEAR THE PROPOSED |
| | WATER UTILITIES OR SUBMIT LANDSCAPING PLAN WITH |
| | RESUBMITTAL PACKAGE. |
| | -SHOW PAVEMENT RESTORATION AREA SIMILAR TO SD GC8 NOTE |
| | 1. |
| | |
| | COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS |
| | EXAMINER, [email protected] , 561-494-1101: |
| | |
| | -SPECIFY WATER SERVICE SIZES AND MATERIALS. |
| | -VERIFY WHICH SEWER LATERAL WILL BE USED, AS THE |
| | WESTERN LATERAL IS BEING CROSSED OVER BY PROPOSED FIRE |
| | HYDRANT. |
| | -SHOW FULL LENGTH OF EXISTING WATER SERVICE AND METER |
| | -8???GRAVITY SEWER MAIN IS LABELED AS FORCE MAIN, |
| | PLEASE CORRECT |
| | -DENOTE SIZE OF GATE VALVE PROPOSED FOR INSTALLATION |
| | -SPECIFY METHOD OF CONNECTION FOR POTABLE AND |
| | IRRIGATION LINES. (TAPPING SLEEVE?) |
| | -CURRENT LOCATION OF WATER METERS WILL REQUIRE A |
| | PROPOSED EASEMENT. |
| | -SHOW ALL EXISTING DRY UTILITIES ON PLAN VIEW |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT (561) 494-1098 [email protected] |
| | |
| | |
| |