Plan Review Notes
Plan Review Notes For Project E23010008
Project Number E23010008
Review Stop ENG-A
Sequence Number 3
Notes
Date Text
2023-05-15 11:34:09NO COMMENTS FROM LINDA M. QUINONES-CINTRON, PROJECT
 COORDINATOR, ENGINEERING SERVICES DEPT., 561-494-1085
 [email protected] :
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -RESPONSE LETTER SAID ALL DETAILS ARE THE LATEST SHOWN
 ON CITY WEBSITE, BUT STILL SEE OLD REVISION WATER
 SERVICE STANDARD DETAIL WS1. SHEET 4 IS SHOWING APR2018
 REVISION, BUT VERIFIED THAT CITY WEBSITE HAS SEP2019
 REVISION. PLEASE REPLACE WITH NEWEST REVISION. AFTER
 UPDATING SHEET 4, ADD MARKUP NOTE ON WS1 THAT DUAL
 CHECK IS NOT USED WHEN A BACKFLOW ASSEMBLY IS BEING
 INSTALLED.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 2023_0502 SITE CIVIL PLAN-SHEET1_S&S (SEE EMAIL
 5.15.2023 FOR SNIPS)
  
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
  
 -REFLECT ALL LATERALS FOUND FROM CCTV ONTO PLAN VIEW
 (INCLUDING THOSE THAT ARE NOT SERVING THE PROJECT
 LOCATION) AND REFLECT REMOVAL UP TO THE MAIN (CUT AND
 CAP) FOR LATERALS THAT ARE NOT TO BE REUSED. (NOTE:
 CCTV LATERAL REPORT MAKES MENTION OF A COUPLE EXISTING
 SERVICES BEING CAPPED, BUT VIDEO EVIDENCE DOESN???T
 APPEAR TO SHOW THAT THE LATERALS WERE CUT AT THE MAIN.
 PLEASE CONFIRM DURING FIELD VERIFICATION OF THESE
 LATERALS, AND CUT/CAP AS NEEDED SHOULD THEY NOT BE.)
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
  
  