Plan Review Notes
Plan Review Notes For Project E23010008
Project Number E23010008
Review Stop ENG-A
Sequence Number 2
Notes
Date Text
2023-04-26 14:20:44E-23010008- 2414 FLORIDA AVE.- 4.03.23 ??? RESUBMITTAL
 REVIEW
  
 NO COMMENTS FROM LINDA M. QUINONES-CINTRON, PROJECT
 COORDINATOR, ENGINEERING SERVICES DEPT., 561-494-1085
 [email protected] :
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
 -STILL HAVE OLD REVISION WPB STANDARD DETAILS ON SHEET
 4. REPLACE ALL OLD REVISION STANDARD DETAILS WITH
 NEWEST REVISION. THEY ARE PUBLISHED ON CITY WEBSITE.
  
 -ON SHEET 1, PLEASE MAKE SURE THAT ALL THE METERED
 WATER SERVICES THAT ARE BEING REMOVED HAVE THE SAME
 CALLOUT TO ADDITIONALLY REMOVE BOX AND REPLACE SIDEWALK
 AS NOTED IN RESPONSE LETTER. SEE ONE OF THEM UPDATED,
 BUT TWO ARE STILL THE SAME.
  
 -ON SHEET 1 ADD GENERAL NOTE FOR CONTRACTOR TO RETURN
 REMOVED WATER METERS TO CITY WPB. CAN CONTACT
 [email protected].
  
 -RESPONSE LETTER SAID STANDARD DETAIL WS4 WAS REMOVED,
 BUT STILL SEE IT ON SHEET 4.
  
 -CONSIDER ADDING REVISION DATES TO PLAN SHEETS.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
  
 1. THE CITY???S OFFICIAL VERTICAL DATUM IS NGVD1929.
 THE CITY HAS ALLOWED PROJECTS TO BE SUBMITTED USING
 NAVD1988 AS THE VERTICAL DATUM PROVIDED THE VERTICAL
 DATUM IS LISTED ON EVERY SHEET WITH ELEVATION
 INFORMATION AND THAT THERE IS A CONVERSION EQUATION
 BETWEEN NAVD1988 AND NGVD1929 ON THE SHEET(S). LIST THE
 VERTICAL DATUM AND CONVERSION EQUATION ON SHEET 5.
 3. THE HANDICAP PARKING SPACE AND THE SOUTHERN-MOST
 PARKING SPACE WILL BE BACKING OUT OVER EXISTING CURB
 INLETS AND WILL NEED TO BE RELOCATED/ELIMINATED. CITY
 DEVELOPMENT CODE SECTION 94-485.J.1 PROHIBITS PARKING
 AND LOADING SPACE CONFIGURATIONS THAT REQUIRE BACKING
 DIRECTLY ONTO A STREET IN ALL RESIDENTIAL AND
 NONRESIDENTIAL ZONING DISTRICTS.
 4. THE HANDICAP SPACE AND ACCESS AISLE ARE LIMITED TO
 2% SLOPE IN ALL DIRECTIONS. NO PROPOSED SPOT GRADES ARE
 SHOWN ON ANY SHEET.
 5. REPLACE THE SIDEWALKS ALONG THE BUILDING FRONTAGES
 TO BE ADA COMPATIBLE IF CURRENT CROSS SLOPE EXCEEDS 2%.
 SHOW THE JOINTS AS NON-SCREENED LINES SO IT STANDS OUT
 AS NEW. CALLOUT ANY SIDEWALK ALONG WESTWOOD ROAD THAT
 WILL BE REPLACED.
 6. THE CURB RAMP ON THE NE CORNER OF FLORIDA AVE AND
 WESTWOOD ROAD WILL NEED TO BE CONSTRUCTED TO CURRENT
 ADA REQUIREMENTS IF THE ASPHALT ADJACENT TO THE RAMP IS
 MODIFIED IN ANY WAY. CALLOUT THE FDOT RAMP
 NUMBER/LETTER AND REFER TO THE CURRENT FDOT STANDARD
 PLAN INDEX NUMBER.
 7. LABEL THE SURFACE MATERIAL BETWEEN THE AREAS BOUNDED
 BY SIDEWALK, STEPS UP TO THE BUILDING AND PARKING
 SPACES (I.E. THIS YELLOW SHADED AREA): (SEE WORD
 DOCUMENT IN EMAIL 4.19.23)
  
  
 8. TYPICAL PARKING LOT STRIPING DETAIL ON SHEET 4 SHOWS
 THE PARKING SPACE DEPTH TO BE 18.5 FEET. THE CITY
 DEVELOPMENT CODE SECTION 94-485 SPECIFIES STANDARD
 90-DEGREE PARKING SPACES AS 8.5 FEET WIDE BY 18 FEET
 DEEP AND SMALL CAR 90-DEGREE PARKING SPACES AS 8 FEET
 WIDE BY 16 FEET DEEP.
 9. PROVIDE A CROSS SECTION FROM THE FACE OF BUILDING TO
 THE CENTERLINE OF FLORIDA AVE. SHOW BREAK POINTS, LABEL
 SURFACE FEATURES, SURFACE SLOPES, RIGHT WAY WITH STREET
 NAME. PROVIDE DISTANCES FROM THE R/W TO EDGE OF ROAD
 PAVEMENT, TO BACK OF SIDEWALK, TO THE ELEVATED SIDEWALK
 NEXT TO THE BUILDING AND TO THE FACE OF THE BUILDING.
 10. SHOW THE EXISTING WATER SERVICES BETWEEN THE WATER
 METER AND WATER MAIN. SHOW THE EXTENT OF ROAD MILLING
 AND RESURFACING PER THE CITY???S TRENCH DETAIL.
 11. DRAW THE VALLEY GUTTER AS BEING 2 FOOT WIDE
 (CURRENTLY SHOWN AS 0.5 FOOT WIDE) AND SHOW THE FLOW
 LINE. THE VALLEY GUTTER TO HAVE POSITIVE DRAINAGE TO AN
 INLET.
 12. WHY IS TYPE ???F??? CURB AND GUTTER BEING
 CONSTRUCTED ALONG WESTWARD ROAD? THE EDGE OF PAVEMENT
 FRONT OF GUTTER IS NOT SHOWN. HOW IS THE STORMWATER
 TREATMENT, CURRENTLY PROVIDED IN THE SWALE, BEING
 REPLACED?
 13. IF THE PARKING LOT IS BEING RECONSTRUCTED THEN
 STORMWATER MANAGEMENT, MEETING SFWMD ERP CRITERIA, WILL
 NEED TO BE PROVIDED ONSITE.
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
 -COMMENT 2 NOT FULLY ADDRESSED. PLEASE SPECIFY THE
 BACKFLOW TYPE, NOT JUST THE SERVICE THAT THE BACKFLOW
 BELONGS TO
 -DENOTE CITY OF WPB???S POINT OF SERVICE FOR BOTH WATER
 AND SEWER
 -PROPOSE PLAN TO MINIMIZE OUTAGES TO CUSTOMERS DURING
 CONSTRUCTION (WILL LINE STOPS, INLINE VALVES, VALVE
 SHUTDOWNS, ETC. BE NECESSARY?)
 -PLEASE COMPLETE CCTV OF SEWER MAIN FROM MANHOLES ON
 WESTWOOD TO UPLAND, OR PROVIDE COMPLETED CCTV AND
 REPORT IN ORDER TO ASSESS CONDITION OF EXISTING PIPE
 AND DETERMINE IF LINING/REPLACEMENT MAY BE NECESSARY
 -LOCATION MAP SHOWS EXTENTS OF PROJECT AS ARDMORE BEING
 THE NORTHERN LIMITS WHILE PLANS ONLY SHOW WORK UP TO
 UPLAND. PLEASE SPECIFY IF WHETHER OR NOT WORK IS BEING
 DONE NORTH OF THE PLAN LIMITS.
 -SHOW ALL EXISTING VALVES AND APPURTENANCES FOR BOTH
 WATER AND SEWER
 -PRINT SHEETS SO THAT THEY ARE TO SCALE ON 11X17 PAPER
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
  