Plan Review Notes
Plan Review Notes For Project E22120012
Project Number E22120012
Review Stop ENG-A
Sequence Number 2
Notes
Date Text
2023-05-01 13:22:32E22120012 - ROYAL POINCIANA PLAYHOUSE RESUB 3.28.23
  
 NO COMMENTS FROM LINDA QUI??ONES-CINTRON, PROJECT
 COORDINATOR, ENGINEERING SERVICES DEPARTMENT (561)
 494-1085 [email protected]:
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
 -PROPOSED WATER DEMAND AVERAGE AND PEAK GPM EXCEED
 THRESHOLDS FOR 1.5 INCH M120 BADGER METER. CANNOT USE
 1.5 INCH DOMESTIC METER. NEED TO RE-EVALUATE WATER
 DEMAND CALCULATIONS OR INCREASE METER SIZE. NEXT METER
 SIZES AND MODELS ARE 2 INCH M170 BADGER METER AND 3
 INCH BADGER COMPOUND METER. PEAK GPM EXCEEDS 2 INCH
 METER AS WELL.
  
 -ADD NOTE ON DEMO PLAN FOR CONTRACTOR TO RETURN REMOVED
 WATER METERS TO CITY WPB. CAN CONTACT [email protected].
  
 -GATE VALVE NEAR TAP FOR 6 INCH FIRELINE IS SHOWING TOO
 CLOSE TO A SIGN. VALVE KEY WILL NOT BE ABLE TO OPERATE
 GATE VALVE.
  
 -REMINDER TO FOLLOWUP ON THE 2 INCH CHILLER LINE ISSUE
 FROM LAST RESPONSE LETTER.
  
 -WATER PLANS DO NOT SHOW THE BE UTILITY AND FPL
 EASEMENTS SHOWN ON SURVEY.
  
 -WATER METER AND BACKFLOW ASSEMBLIES AT NORTH SIDE OF
 150 ROYAL POINCIANA STILL NEED BE RELOCATED
 SIGNIFICANTLY EAST. TO ACCOMPLISH THAT MAY NEED REVISE
 LANDSCAPING PLANS. WOULD NEED UTILITY EASEMENT AROUND
 METER BOX IF ON PRIVATE PROPERTY AND NO UTILITY
 EASEMENT CURRENTLY EXISTS THERE.
  
 -OVERALL LANDSCAPING PLAN SHOWS TWO ADDITIONAL
 TRANSFORMERS NEAR PROPOSED 3 INCH FIRELINE BACKFLOW
 ASSEMBLY AND PIPING. UPDATE ENGINEERING PLANS IF
 TRANSFORMERS ARE SHOWN ACCURATELY ON LANDSCAPING PLAN.
  
 -ADD WATER SERVICE LINE PIPE SIZE AND MATERIAL TYPE
 UPSTREAM OF PROPOSED WATER METER.
  
 -ON LABELS OF PROPOSED BACKFLOW ASSEMBLIES AND WATER
 METERS, ADD REFERENCE TO THE ASSOCIATED WPB WATER
 SERVICE STANDARD DETAIL.
  
 -PLANS NEED BE SIGNED, SEALED, AND DATED.
  
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected], 561-494-1101:
  
 -COMMENT 2 NOT FULLY ADDRESSED. PLEASE DENOTE THE POINT
 WHERE WPB TAKES OVER MAINTENANCE OF SERVICE. (LINE
 CANNOT BE CONSIDERED ???PRIVATE??? AS DISCUSSED ON
 PHONE CALL)
 -COMMENT 5 NOT FULLY ADDRESSED, PLEASE PROVIDE THE
 PROFILE REGARDLESS OF LENGTH IN ORDER TO DETERMINE LACK
 OF CONFLICTS AND APPROPRIATE CLEARANCE FOR THE PROPOSED
 PIPE.
 -COMMENT 8 NOT FULLY ADDRESSED, PLEASE REVISE.
 (CONFIRMATION GIVEN ON WATER DISTRIBUTION
 DEPARTMENT???S END ON PREFERENCE FOR SEPARATE TAPS)
 -REAPPLY ALL INFO RELATING TO DRY UTILITY LOCATIONS ON
 THE PLAN VIEW
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 LINDA QUI??ONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
  
  