| Plan Review Notes For Project E22120001 |
| Project Number |
E22120001 |
|
| Review Stop |
ENG-A |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-13 14:24:44 | E22120001 - IMECA HARDWARE, 3200 45TH ST - 3.3.2023 | | | RESUB | | | | | | NO COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, | | | ENGINEERING SERVICES DEPT., 561-494-1098 | | | [email protected] : | | | | | | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR | | | [email protected]: | | | | | | -SHEET C6 IS UNREADABLE. PLEASE CORRECT AND RESUBMIT. | | | -SHEET C13 HAS AN ERROR WITH THE SHEET NUMBER. PLEASE | | | REVISE. | | | -DOWNSTREAM VERTICAL LEG OF DCDA SHOULD ALSO BE DUCTILE | | | IRON BEFORE IT TRANSITIONS TO PVC. PLEASE CALLOUT THAT | | | PIPE SEGMENT MATERIAL ON PROFILE. | | | -DIGITAL SIGNATURE REFERENCES DATE ADJACENT TO SEAL. | | | PLEASE VERIFY DATE IS CORRECT. | | | | | | NO COMMENTS FROM TRACY WARD, SR. STORMWATER ENG., | | | ENGINEERING SERVICES, [email protected] 561-494-1120: | | | | | | COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES ENGINEER, | | | [email protected], 561-494-1101: | | | | | | -SECOND GATE VALVE WITHIN EASEMENT FOR FIRE LINE WILL | | | BE REQUIRED | | | -CURRENT TAP LOCATION EXHIBITS GATE VALVE LOCATED ON | | | CURB. PLEASE RECONFIGURE DESIGN | | | -DOUBLE CHECK THE LOCATION OF THE WATER METER PROPOSED | | | FOR CONNECTION. | | | |
| |