Plan Review Notes
Plan Review Notes For Project E22120001
Project Number E22120001
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2023-01-06 11:20:55E22120001 - IMECA HARDWARE, 3200 45TH ST - 11.30.22
 SUBMITTAL REVIEW ??? PARTIAL COMMENTS
  
 COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
  
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 3. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER.
 4. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 5. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 6. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND
 IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS,
 AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. GATE
 VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR SIDEWALK.
 ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE
 VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON
 PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. PLEASE
 SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPES SIZES AND
 MATERIALS, LOCATED ON THE RIGHT-OF-WAY.
 7. PLEASE CUT AND CAP UTILITIES NOT IN USE AND REMOVE
 ANY ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM
 CITY RIGHT OF WAY.
 8. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS,
 INCLUDING THOSE PROPOSED TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITY WATER METERS.
 9. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION, AND
 EXISTING METER AND BACKFLOW (TO BE REMOVED?). BACKFLOWS
 SHALL BE INSTALLED ON PRIVATE PROPERTY OUTSIDE OF
 EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER METERS
 SHALL BE INSTALLED IMMEDIATELY ADJACENT TO PROPERTY
 LINE. 3 INCH AND LARGER WATER METERS SHALL BE INSTALLED
 ABOVE-GROUND ONLY.
 10. ENGINEERING PLANS SHALL INCLUDE PIGGING, FLUSHING
 AND SAMPLE POINTS ON ANY WATER RUNS 60 FT. IN LENGTH OR
 GREATER.
 11. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 12. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES AT ALL UTILITY CROSSINGS WITHIN ROW PER
 CITY OF WEST PALM BEACH STANDARD DETAIL GN-2 SERIES.
 PLEASE SHOW ALL EXISTING AND PROPOSED UNDERGROUND
 UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS,
 AND CABLEVISION & TELECOMMUNICATION FACILITIES WITH
 PIPE MATERIAL AND SIZE, LOCATED ON THE RIGHT-OF-WAY.
 13. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 14. PLEASE CLEARLY LABEL ROAD RIGHT OF WAY.
 15. REPAIR SIDEWALK AND PAVEMENT RESTORATION PER PALM
 BEACH COUNTY STANDARD DETAILS, NOT CITY (UPDATE NOTE ON
 SHEET C-8).
 16. SOME NOTE LEADERS ARE NOT PLACED ACCURATELY ON
 SHEET C-8.
 17. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 18. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
  
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
 -SHEET C2 UTILITY CONNECTION NOTE 6 NEEDS REVISION. NOT
 SURE IF MEANT CITY OF WEST PALM BEACH OR PALM BEACH
 COUNTY.
  
 -SHEET C8 UTILITY CONNECTION ENLARGEMENT: EXISTING BFP
 LABEL SHOULD SAY TO REMOVE; CALLOUT MINIMUM 3 FEET
 HORIZONTAL DISTANCE BETWEEN UTILITY POLE AND WATER
 METER BOX; ADD VISUAL SCALE MEASUREMENT ICON; FIRELINE
 BACKFLOW IS CALLED OUT AS DCDA BUT C2 WATER
 DISTRIBUTION NOTE 3 SAYS SHOULD BE RPDA.
  
 -SHEET C8 UTILITY CONNECTION ENLARGEMENT: RELOCATED 1
 INCH METER MUST HAVE COMPLIANT SERVICE LINE. ADD
 REFERENCE TO STANDARD DETAIL WS1 ON LABEL AND DESIGNATE
 PIPE MATERIAL TYPE TO USE.
  
 -SHEET C8 UTILITY CONNECTION ENLARGEMENT: SHOW SYMBOL
 FOR GATE VALVE FOR FIRELINE. ALSO CALLOUT PIPE MATERIAL
 TYPE FOR FIRELINE (IT MUST BE DIP FROM MAIN TO DCDA.
 MAY NEED TO UPDATE SHEET C2 ALSO.)
  
 -CLEANOUTS DO NOT HAVE RIM AND INVERT ELEVATIONS ON THE
 LABELS.
  
 -SHEET C11 HAS NOTE ABOUT H20 METER BOXES. WPB AML
 SMALL WATER METER BOXES ARE NOT H20 RATED. STANDARD
 TRAFFIC RATING SHOULD BE ACCEPTABLE.
  
 -ADD FIRE FLOW CALCULATIONS AS DIRECTED ON SHEET C12 SD
 WS5 NOTE 9 TO EITHER WATER OR UTILITY PLAN SHEETS
 VERIFYING FIRELINE WILL MEET DEMAND OF PRIVATE FIRE
 SYSTEM.
  
 -IS A HEALTH PERMIT NEEDED OR REQUIRED?
  
 -SHOW SAMPLE POINT LOCATIONS IF ANY ARE NEEDED OR
 REQUIRED.
  
 -ADD STANDARD DETAIL P1 AND WS2 TO PLAN SET. IF
 SAMPLING, ADD WPB SAMPLE POINT DETAIL TO PLAN SET. IF
 PIGGING OR NEED JUMPER, THEN ADD STANDARD DETAIL P6 TO
 PLAN SET.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 1. DRIVEWAY APRON WITHIN THE RIGHT OF WAY TO BE 6???
 THICK CONCRETE UNLESS THE COUNTY WILL ALLOW ASPHALT
 (45TH ST IS COUNTY R/W).
 2. IDENTIFY ON SHEET C-6 WHERE SECTIONS A-A THROUGH D-D
 AND THE PROPOSED DRIVEWAY PROFILE ARE LOCATED.
 3. SHOW AND CALLOUT DROP CURB ON SHEET C-6 AND ON THE
 PROPOSED DRIVEWAY PROFILE ON SHEET C-9.
 4. CORRECT THE TEXT OVERLAP INSIDE THE BUILDING ON
 SHEET C-8.
 5. ON SHEETS C-8 AND C-11, LABEL THE EXISTING FIRE
 HYDRANT ON THE ADJACENT LOT AS ???PRIVATE???.
 6. A COUNTY PERMIT WILL BE NEEDED FOR THE WORK WITHIN
 THE 45TH STREET R/W.
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES ENGINEER,
 [email protected], 561-494-1101:
  
 -PROPOSED VALVE FOR FIRE LINE TAP NOT SHOWN ON THE
 PLANS
 -VERIFY EXISTING NORTH/SOUTH RUN OF SEWER THAT HAS
 PROPOSED CONNECTION ON THE PLANS. LATERAL IS NOT SHOWN
 ON GIS OR AS-BUILTS.
 -SEWER MATERIAL NEEDS TO BE CALLED OUT
 -MATERIALS FOR WATER LINE AND FIRE LINE NEED TO BE
 CALLED OUT
 -POINTS OF SERVICE ARE AS FOLLOWS: METER FOR 1??? LINE,
 GATE VALVE FOR FIRE LINE, CLEANOUT FOR SEWER LATERAL
 -SLOPE FOR SEWER LATERAL NOT LISTED
 -FIRE LINE MAY NEED TO BE TAPPED ELSEWHERE AS TO AVOID
 GATE VALVE BEING INSTALLED WITHIN SIDEWALK
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT (561) 494-1098 [email protected]
  