| 2022-12-09 14:21:00 | E22090007 - MINT ECO 10.25.22 RESUB REVIEW |
| | |
| | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPT., 561-494-1098 |
| | [email protected] : |
| | |
| | SPECIFY PIPE SIZE AND MATERIAL OF WATER LINE BEING |
| | TAPPED AT CONNECTION AND ADD TO PLAN AND BLOW-UP DETAIL |
| | A. |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR |
| | [email protected]: |
| | |
| | -REMINDER TO ADD MEP PLANS IN RESUBMITTAL PACKAGE AS |
| | REFERRED TO IN RESPONSE LETTER. |
| | |
| | -VERIFY THERE WILL BE NO FIRE SPRINKLERS IN BUILDING. |
| | |
| | -SEWER CLEANOUT BEHIND DUMPSTER AREA MAY CONFLICT WITH |
| | PROPOSED PLANTS FROM LANDSCAPING PLAN. CHECK AND |
| | COORDINATE WITH LANDSCAPING PLAN DESIGNER AS NECESSARY. |
| | |
| | -WATER AND SEWER DEMAND CHART HAS REFERENCES TO MANY |
| | BEDROOMS AND DWELLING UNITS. PLEASE VERIFY AND UPDATE |
| | THE INFORMATION AS NEEDED. |
| | |
| | -IF CAR WASH HAS A DESIGNATED ADDRESS, THEN PLEASE ADD |
| | TO PLANS. |
| | |
| | COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS |
| | EXAMINER, [email protected] , 561-494-1101: |
| | |
| | IS A WATER SERVICE LINE BEING REMOVED? IF SO, SHOW ON |
| | PLANS. |
| | |
| | -DENOTE INVERT FOR PROPOSED SEWER LATERAL AS POINT OF |
| | SERVICE (OR ADD CLEANOUT BEFORE OR JUST WITHIN PROPERTY |
| | LINE). |
| | |
| | -SHOW DIRECTION OF FLOW FOR EXISTING SANITARY LINE. |
| | |
| | -PROVIDE A PROFILE FOR SEWER LATERAL TO SHOW SEPARATION |
| | OF DRY UTILITIES. |
| | |
| | |
| | COMMENTS FROM TRACY WARD, SR. STORMWATER ENG., |
| | ENGINEERING SERVICES, [email protected] 561-494-1120: |
| | |
| | 1. REVISE THE PIPE MATERIAL HDPE TO RCP IN THE |
| | CONNECTION NOTE TO THE EXISTING CATCH BASIN AT INVERT |
| | ELEVATION 10.9N. |
| | 2. STRUCTURE A8 ??? INDICATE WHICH INVERT WILL BE |
| | COVERED BY THE PRB. |
| | 3. STRUCTURE A6 SHOULD HAVE TWO PRBS. |
| | 4. CONTROL STRUCTURE A1 DETAIL: |
| | A. SECTION VIEW SHOWS FRAME AND GRATE BUT LABEL CALLS |
| | OUT USF 620- GRATE / NO FRAME (TYPE ???E???) |
| | B. CONFIRM USF 620 GRATE INSTEAD OF USF 6290, 6300 OR |
| | 6616. (COMMENT ALSO PERTAINS TO THE STANDARD TYPE |
| | ???C??? & ???E??? INLET DETAIL). |
| | 5. TEXT OVERLAP ON THE CITY DETAIL ST-7. |
| | 6. SHOULDN???T RECLAIM WATER TANKS BE CONNECTED TO THE |
| | SAND/OIL SEPARATOR? SHOULD DOMESTIC SEWER LINE FLOW |
| | THROUGH THE SAND/OIL SEPARATOR? |
| | 7. WHAT ARE THE DIMENSIONS OF THE 1500 GALLON RECLAIMED |
| | WATER TANKS? |
| | 8. PROVIDE SWALES ALONG PROPERTY LINES TO PREVENT |
| | DIRECT RUNOFF TO ADJACENT PROPERTY OR TO PALM BEACH |
| | LAKES R/W. |
| | |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT (561) 494-1098 [email protected] |
| | |
| |