Plan Review Notes
Plan Review Notes For Project E22100023
Project Number E22100023
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2023-02-07 08:39:47E22100023 - BALTIMORE GALLERIA 165 BRADLEY PL ??? RESUB
 1.20.2023
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -HISTORIC PICTURES OF AREA SHOW TRAFFIC SIGN NEAR CURB
 CLOSE TO PROPOSED AREA OF FIRELINE. SHOW AND LABEL ON
 PLANS IF STILL THERE AND ENSURE SUFFICIENT HORIZONTAL
 CLEARANCE BETWEEN PIPE AND POLE.
 -HISTORIC PICTURES SHOW LARGE BUSHES IN PROPOSED DCDA
 LOCATION. ADD NOTE FOR BUSHES AND TREES TO BE DISTANCED
 MINIMUM 18 INCHES AWAY FROM FIRELINE BACKFLOW AND GATE
 VALVES.
 -CHECK CONTINUITY CALLOUT ON PROFILE 1. THINK IT SHOULD
 SAY PROFILE 2.
 -ADD NOTE THAT BACKFLOW HEIGHT MUST MEET REQUIREMENT OF
 WS5.
  
 COMMENTS FROM RICKY ELIZONDO, E.I., UTILITIES PLANS
 EXAMINER, PUBLIC UTILITIES [email protected]
 561-764-8010 (CELL)
 CALL OUT THE SAMPLE POINTS ON THE FIRE LINE.
  