Plan Review Notes
Plan Review Notes For Project E18060023
Project Number E18060023
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2018-07-30 11:15:57SHEET C3.00 -
 1) AT WESTERNMOST PB LAKES BLVD. DRIVEWAY, CONFIRM THAT
 FLARES ARE ADA COMPLIANT.
 2) WHY IS THE WESTERNMOST PB LAKES BLVD. DRIVEWAY A
 RIGHT TURN ONLY?
 3) ELIMINATE PARKING SPACE JUST WEST OF THE WESTERNMOST
 PB LAKES BLVD. DRIVEWAY. ADD LANDSCAPE ISLAND TO
 PROVIDE SAFE SIGHT DISTANCE. REDLINED PLANS ARE
 AVAILABLE FOR PICKUP.
 4) CHANGE SIDEWALK WIDTHS TO 8 FT. (DOWNTOWN CODE
 REQUIREMENT).
 5) REMOVE INBOUND ARROW AT EASTERNMOST PB LAKES BLVD.
 DRIVEWAY.
 6) EXTEND LANDSCAPE ISLAND AT THE SW CORNER PB LAKES
 BLVD. AND OLIVE AVE. REDLINED PLANS ARE AVAILABLE FOR
 PICKUP.
 7) REBUILD CURB AT SW CORNER OF PB LAKES BLVD. AND
 OLIVE AVE. FOR BIKE LANE CONTINUITY.
 8) HOW WILL BIKES BE DETECTED AT THE SIGNAL AT PB LAKES
 BLVD. AND OLIVE AVE.? WILL LOOPS NEED TO BE
 DISCONNECTED?
 9) PLEASE PROVIDE SEPARATE SIGNING & MARKING PLANS.
 10) PROVIDE AERIAL PHOTO THAT INCLUDES AREA EAST OF
 OLIVE AVE.
 11) ADD CROSSHATCHING ALONG PB LAKES BLVD. PARKING TO
 ACCOMMODATE DOOR ZONE BUFFER. REDLINED PLANS ARE
 AVAILABLE FOR PICKUP.
 12) ADD BIKE LANE SIGNING AND MARKING.
 13) RESURFACE WHERE PAVEMENT MARKINGS ARE BEING
 REMOVED. SHOW LIMITS OF MILLING & RESURFACING.
 14) AT EASTERNMOST DRIVEWAY ON PB LAKES BLVD., TIGHTEN
 EASTERN RADIUS TO DISCOURAGE RIGHT TURN EGRESS.
 REDLINED PLANS ARE AVAILABLE FOR PICKUP.
 15) REMOVE ARROWS FROM ALLEY ON SOUTH SIDE OF PROJECT.
 ALLEY IS BI-DIRECTIONAL.
  
 PLEASE RESPOND TO ALL COMMENTS IN WRITING.
  
 COMMENTS PER ERIK FERGUSON
 CITY TRANSPORTATION ENGINEER
 ENGINEERING SERVICES
 561-494-0192
2018-07-30 10:08:00COVER SHEET- CITY OF WPB CONTACT NAME FOR LAURA LE, PE
 NEEDS CORRECTION.
 COVER SHEET - PROVIDE ADDRESS FOR THE BUILDING.
 SHEET C0.02 SURVEY DATA NOTE: NEEDS TO CALL OUT CITY
 VERTICAL DATUM IS NGVD 29. PROVIDE CONVERSION EQUATION.
 SHEET C0.02 AS-BUILT NOTES NEED TO REQUEST PDF AND CAD
 FILES FROM SURVEYOR.
 SHEET C1.00 EROSION CONTROL NOTES NEED TO DIRECT THE
 CONTRACTOR TO PERFORM INSPECTION AFTER RAIN EVENTS AND
 INTERVAL INSPECTIONS PER NPDES, EVERY 7 DAYS. KEEPING A
 LOG ON-SITE.
 SHEET C1.00 SITE SLOPES NORTH AND EAST. PROVIDE SHORING
 OR DOUBLE SILT FENCE ON POLLUTION PREVENTION PLAN ALONG
 NORTH SIDE AND EAST SIDE OF PROPERTY. OR ALTERNATE BMP
 OPTIONS CAN BE SUBSTITUTED.
 NOTE 19 OF CALLS OUT DEWATERING ACTIVITIES. PROVIDE
 DEWATERING SEQUENCE OR REMOVE THE NOTES.
 SHEET C2.00 MILL AND RESURFACE DOES NOT CALL THICKNESS
 OF ASPHALT. FOR ALLEYWAYS MILLING AND RESURFACING 1" IS
 THE MINIMUM STANDARD THE CITY ACCEPTS.
 SHEET C2.00 DRIVEWAY APRON EXITING TO NORTH OLIVE FROM
 ALLEYWAY NEEDS TO HAVE DETECTABLE WARNING SURFACE ON
 BOTH SIDES FOR PEDESTRIAN CROSSING. PAVERS ALSO NEED TO
 BE RESET.
 SHEET C2.00 CALL OUT MAINTENANCE AGREEMENT FOR THE N.
 OLIVE ROW AND PALM BEACH LAKES BOULEVARD. THIS INCLUDES
 IRRIGATION, AND ANY ELEMENTS IN THE ROW RELATED TO THE
 BUILDING.
 SHEET C2.00 PROVIDE A STRUCTURE AT THE END OF THE
 PROPOSED CAP OF THE DRAINAGE FOR THE BURGER KING FOR
 ACCESS AND MAINTENANCE OF THEIR SYSTEM. NOTE THAT IF
 THE LINE IS AN EXFILTRATION THAT CONTRACTOR SHALL
 NOTIFY THE EOR TO EVALUATE AND PROVIDE ADDITIONAL
 EXFILTRATION NEEDED TO THAT SITE.
 SHEET C2.00 DEMOLITION NOTE 19 CALLS OUT PALM BEACH
 COUNTY INSTEAD OF THE CITY. IT SHOULD ALSO MAKE THE
 DISTINCTION THAT ANY DRAINAGE MODIFICATION ON PALM
 BEACH LAKES SHALL BE COORDINATED WITH PALM BEACH COUNTY
 ROADWAYS' APPROVAL AND INSPECTION, LIKE THE STORM WATER
 TIE-IN AT THE NE CORNER OF THE SITE.
 PROVIDE PALM BEACH COUNTY TRAFFIC APPROVAL FOR
 RECONFIGURATION OF PALM BEACH LAKES BLVD.
 SHEET C4.00 CALL OUT ROOF DRAINS. RAIN LEADERS TIED TO
 DRAINAGE SHALL BE SHOWN.
 SHEET C4.00 GRADE CHANGE ABUTTING THE ALLEYWAY WILL
 REQUIRE TRENCH DRAINS TO RETAIN WATER ON-SITE.
 SPECIALLY AT DRIVEWAY EXCITING TO ALLEY AND SANITATION
 AREA.
 SHEET C4.00 SANITATION AREA WILL REQUIRE NOTATION: IT
 WILL BE THE OWNERS RESPONSIBILITY TO ROLL OUT DUMPSTER
 FOR CITY PICKUP. A DIFFERENCE IN FLOOR ELEVATION SHOWS
 A 6" DROP. IT'S QUESTIONABLE HOW IT WILL BE ROLLED OUT.
 SHEET C4.00 IDENTIFY AREA ADJACENT TO PALM BEACH LAKES
 JUST WEST OF PEDESTRIAN ACCESS TO PARKING GARAGE.
 SHEET C4.00 SHOW GRADE ELEVATIONS AROUND METER AND
 BACKFLOWS AREA. AREA MUST BE STABILIZED AND FLAT FOR
 THE PLACEMENT OF THESE APPARATUSES.
 SHEET C4.00 PROVIDE 6" CURBING BEHIND DRIVEWAY RAMPS TO
 ALLOW BETTER CONTAINMENT AT STEEP SLOPES.
 SHEET C4.00 PROVIDE MORE INFORMATION ON STORMWATER
 STRUCTURE WHERE YOU WILL TIE ON PALM BEACH LAKES. TYPE
 OF STRUCTURE, SIZE, DIAMETER...
 SHEET C4.00 DRAINAGE PIPE CONNECTION OUT TO PALM BEACH
 LAKES DOES NOT CALL OUT MATERIAL OF PIPE. IN THE CITY
 ANY PIPES CONNECTIONS OUT IN THE ROW SHALL BE OF
 REINFORCED CONCRETE PIPE (RCP)
 PROVIDE INFORMATION IF THERE IS WATER AVAILABLE TO
 SITE? FOR CONSTRUCTION? IF NO WATER PRESENT, INSTRUCT
 CONTRACTOR IN A NOTE TO OBTAIN A CONSTRUCTION METER AT
 HIS EXPENSE FROM CITY OF WPB PUBLIC UTILITIES
 DEPARTMENT.
 SHEET C5.00 USE SPELL CHECK ("ALLEY").
 SHEET C5.00 PROVIDE 10 FT. MIN. HORIZONTAL DIMENSION
 BETWEEN SEWER MAIN IN ALLEY AND PROPOSED FIRE LINE.
 SHEET C5.00 PROVIDE WATER AND SEWER DEMANDS PER FAC
 RULE 64E
 SHEET C5.00 PROVIDE WATER AND SEWER VERTICAL
 SEPARATION. (SANITARY LATERAL AND PRIVATE FIRELINE.)
 SHEET C5.00 VERIFY SEWER LATERAL SLOPE OF 1.0% MIN
 SLOPE.
 SHEET C5.00 EXISTING SEWER IS CALLED OUT AS RCP
 MATERIAL THROUGH THE PLAN. TYPICALLY THE MATERIAL
 THROUGHOUT THE CITY THAT WAS USED FOR SANITARY PIPES IS
 VCP (CLAY PIPE). VERIFY WITH AS-BUILDS CONTACTING THE
 CITY'S CAD GROUP FORMAL AS-BUILT REQUEST. CONTRACTOR TO
 VIDEO EXISTING MAIN SANITARY LINE BEFORE AND AFTER
 TIE-IN. PLEASE MAKE NOTATION ON THE PLANS FOR THE
 CONTRACTOR TO FOLLOW.
 SHEET C5.00 WILL TRANSFORMER / PAD WILL BE OWNED AND
 MAINTAINED BY FPL OR PRIVATE. IF IT IS A PRIVATE
 ELEMENT THEN PLACEMENT OF SUCH ELEMENT SHALL BE OUTSIDE
 OF EASEMENT.
 SHEET C5.00 CALL OUT 4 IN. DIAMETER PIPE AND MATERIAL
 COMING INTO THE SITE. CALL OUT NOTE TO BE RESTRAINT
 BACK TO MAIN AS PER CITY OF WPB PIPE RESTRAINT
 STANDARDS. PROVIDE AN ENLARGED VIEW OF THE METER AREA
 SHOWING DOMESTIC AND IRRIGATION METERS. CALLING OUT 3
 IN. POTABLE WATER SERVICE CONFUSES.
 SHEET C5.00 CONFIRM (1) 2 IN. DOMESTIC WATER METER (1)
 1 1/2 IN. IRRIGATION AND (1) 8 IN. DIAMETER PRIVATE
 FIRELINE. NOT A 3 IN. DOMESTIC WATER METER...
 SHEET C5.00 SHOWS A "SUMP PUMP". EXPLAIN WHERE WILL
 THIS TIE INTO. NOTE: IT CANNOT BE TIED TO STORM WATER.
 SHEET C5.00 DETECTABLE WARNINGS SHALL BE INSTALLED AT
 ALLEYWAY PEDESTRIAN EXIT AND AT DRIVEWAY FROM ALLEY
 UNTO N. OLIVE.
 SHEET C5.00 VERIFY ADA COMPLIANT WIDTH / PATH ALONG
 PALM BEACH LAKES BETWEEN EXISTING POLES.
 SHEET C5.00 UTILITY NOTE #7 WATERMAIN CLASS 350 PIPE IS
 CALLED OUT, CITY WILL ACCEPT CLASS 52 DUCTILE IRON PIPE
 IN THE ROW UP TO THE DCDA.
 SHEET C5.00 CALL OUR EXISTING WATERMAINS SIZE AND
 MATERIALS ON PALM BEACH LAKES. TYPICALLY EXISTING
 WATERMAIN ARE COMPOSED OF CAS CAST IRON PIPES.
 SHEET C5.00 CALL OUT CLEARANCE BETWEEN GAS MAIN AND
 FIRELINE AND SANITARY SEWER LATERAL ON N. OLIVE
 RIGHT-OF-WAY.
 SHEET L1.00 EXPLAIN HOW WILL FG TREES PLANTED ALONG
 PALM BEACH LAKES WILL NOT INTERFERE WITH EXISTING STORM
 WATER PIPES BELOW. ROOT BARRIER? STRUCTURAL SOIL? PALM
 BEACH COUNTY ROADWAY APPROVED?
 SHEET L1.00 SHOW A CATCH BASIN IN THE PLACE WHERE A
 ELEVATED MANHOLE IS SHOWN ON SHEET C4.00
  
 PLEASE RESPOND TO ALL COMMENTS IN WRITING. THANK YOU!
  
 COMMENTS PER MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  
  
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved